50
figure 5-5
Configuration of Dip Switch (N≥15)
The length of the RS485 cable and twisted pair cable should be no longer than
1,200m.
If multiple inverters are connected to the data collectorLogger3000, the number of
permissible daisy chains and the number of devices allowed to be connected
should meet the requirements (refer to the user manual for the Logger3000).
5.10.3 Connection Procedure(Terminal Block)
RS485 communication cables should be shielded twisted pair cables or shielded
twisted pair Ethernet cables.
There are four RS485 communication terminals COM1, COM2, COM3and COM4
on the bottom of the inverter. Please choose according to the actual situation.
step 1 Strip the protection layer and insulation layer by appropriate length.
step 2 Loosen the swivel nut of the communication terminal and select an appropriate seal accord-
ing to cable outer diameter. Lead the cable through the swivel nut and seal successively.