Active Power Regulation
table 7-7 Active Power Regulation
Parameter
Definition/Setting
Description
Range
Active power soft start
after fault
The switch for enabling/dis-
abling the soft start function
after a fault occurs.
Enable/Disable
Active power soft start
time after fault
Time that the soft start takes to
raise the power from 0 to
100% rated power.
1s~1200s
Active power gradient
control
Switch for enabling/disabling
the active power rate settable
function.
Enable/Disable
Active power decline
gradient
The decline rate of inverter ac-
tive power per minute.
3%/min~6000%/min
Active power rising
gradient
The rise rate of inverter active
power per minute.
3%/min~6000%/min
Active power setting
persistence
Switch for enabling/disabling
the function of saving output
limited power.
Enable/Disable
Active power limit
The switch for limiting output
power.
Enable/Disable