![Sungrow SG250HX-US Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/sungrow/sg250hx-us/sg250hx-us_user-manual_1396704052.webp)
42
Please use the DC terminal within the scope of delivery or purchase the PV con-
nector according to the recommended model below. Equipment damage caused
by the use of unmatched terminals is not covered by the warranty.
•
If the cross-sectional area of the DC cable is 4/6mm
2
, use the PV connector
within the scope of delivery. The recommended model of the female cable con-
nector is PV-KST4-EVO 2 / 6I-UR (Stäubli), and the recommended male cable
connector is PV-KBT4-EVO 2 / 6I-UR (Stäubli).
•
If the cross-sectional area of the DC cable is 10mm
2
, users need to prepare the
PV connector by themselves or order it from SUNGROW. The recommended
model of the female cable connector is PV-KBT4-EVO 2 / 10II-UR (Stäubli), and
the recommended male cable connector is PV-KST4-EVO 2 / 10II-UR (Stäubli).
step 1 Strip the insulation from each DC cable by 8 mm~10 mm.
step 2 Assemble the cable ends with the crimping pliers.
1: Positive crimp contact
2
:
Negative crimp contact
step 3 Lead the cable through cable gland, and insert the crimp contact into the insulator until it
snaps into place. Gently pull the cable backward to ensure firm connection.
step 4 Tighten the cable gland and the insulator.
User Manual
Содержание SG250HX-US
Страница 2: ......
Страница 6: ......
Страница 10: ......
Страница 36: ...26 End 4 Mechanical Mounting User Manual...