71
Parameter
Definition/Setting
Description
Range
Active power limit ratio
The ratio of limiting output
power to rated power in
percentage.
0%~100%
Shutdown when active
power limit to 0%
Switch used to determine
whether the inverter is in stop
state when the limited power
reaches 0.
Enable/Disable
Reactive Power Regulation
Tap
Settings→Power Regulation Parameters→Reactive Power Regulation
to enter the
screen, as shown in the following figure.
figure 7-16
Reactive Power Regulation
table 7-8 Reactive Power Regulation
Parameter
Definition/Setting
Description
Range
Reactive power genera-
tion at night
Switch for enabling/disabling
night SVG function.
Enable/Disable
Reactive power ratio at
night
Reactive power ratio set for
the night SVG function.
-100%~0%/
0%~100%
Reactive power setting
persistence
Switch for enabling/disabling
the power-off function during
reactive power.
Enable/Disable
Reactive power regula-
tion mode
—
Off/PF/Qt/Q(P)/Q(U)
Reactive power
regulation
Switch for enabling/disabling
reactive response function.
Enable/Disable
User Manual