94
13 Appendix
13.1
MV Station System Parameter
13.1.1
Input data (DC side)
Parameter
Specification
Max. DC voltage
1500Vdc
Startup voltage
840V
MPPT voltage range under full load
800V~1300V
Min. DC voltage
800V
Max. DC power
2800kW
Max. input current
3508A
13.1.2
Output data (Grid side)
Parameter
Specification
Nominal output power
2500kW
Max. continuous output power
2750kW @45
℃
; 2500kW @50
℃
;
Max. continuous output current
46A
Nominal output voltage
34.5KV
Operating voltage range
30.36~37.95KV
Nominal grid frequency
60Hz
Operating frequency range
59.8~60.5 Hz
THD
<3% at nominal power
DC current injection
<0.5% at nominal output current
Output power factor rating
0.99
13.1.3
Mechanical parameters
Parameter
Specification
Dimensions(W×H×D)
238.50inch*114.02inch*95.98inch
(6058mmx2896mmx2438mm)
Weight
39683.20lb (18,000kg)
13.1.4
System data
Parameter
Specification
Max. efficiency
98.8%
CEC efficiency
98.5%
Protection Class
TYPE 3R
Operating temperature range
-22
°
F to140
°
F(>122
°
F derating)
-30
℃
to
+
60
℃
(>50
℃
derating)
Cooling method
Temperature controlled air cooling
Relative humidity
0
~
95% (non-condensing)
Max. working altitude
13123ft(>6561ft derating) 4000m (>2000m derating)
Communication port/protocol
RS485, Modbus, Internet