System Manual
9 LCD Menu Operation
57
9.10
Starting/Stopping
Usually, the MV Station will start automatically when the grid-connected
requirements are met.
Follow either of the two ways below to start/stop the MV Station through the LCD screen:
Tap
“Start/Stop” from the default menu.
Tap
“Start/Stop” from the Function menu.
Start or stop all the two modules at the same time by tapping the start/stop button on the
screen.
A confirm operation interface will appear after tapping the corresponding buttons. The
instruction is effective after confirmation; cancel the operation by tapping
“Cancel”.
9.11
Load Default
Proceed as follows to perform the load default:
Step 1
Tap “Function” from the default menu;
Step 2
Tap “Set-parameter”;
Step 3
Tap “Sys-parameter” after entering the correct password;
Step 4
Tap “Load default” and the password inputting window appears;
The password is “1111”. The system will be reset after entering the password.
9.12
Firmware Version Checking
User can view the firmware version of LCD and DSP as follows:
Step 1
Tap “Function” from the default menu;
Step 2
Tap “Set-parameter”;
Step 3
Tap “Sys-parameter” after entering the correct password;