9.9.13 Forward GOOSE Service Configuration
"Forward GOOSE Service Configuration" is used to configure the Forward GOOSE
Service of Logger4000.
step 1
Click "System"->"Transfer Configuration"->"GOOSE" to enter the "GOOSE" interface.
step 2
Click
on the operation bar to export the GOOSE data configuration file to local.
step 3
Decompress the exported package, and open the . cfg file using Excel in the package.
View and modify the GOOSE data configuration file.
step 4
Save the modified GOOSE data configuration file.
step 5
Click
on the operation bar, select the modified GOOSE data configuration file, and
click "Open" to import it.
-- -- E
En
nd
d
9.9.14 Interface
Set ports of the Logger4000 on the interface. There are 7 RS485 ports (COM1~COM7)
and 1 PLC port.
9.9.14.1 RS485
step 1
Click "System" -> "Interface" -> "RS485" to enter the corresponding interface.
step 2
Click
to modify baud rate, parity bit, and stop bit.
S
Se
erriia
all P
Po
orrtt
B
Ba
au
ud
d R
Ra
atte
e
C
Ch
he
ec
ckk B
Biitt
S
Stto
op
p B
Biitt
P
PL
LC
C
A
Ac
cc
ce
essss
F
Fa
asstt
S
Sc
ch
he
ed
du
ulliin
ng
g
S
Sw
wiittc
ch
h
COM1~CO-
M7
9600
Null
1
Disable/
Enable
Disable/
Enable
When a serial port of Logger4000 is connected to a device, the "Baud rate", "-
Check bit", and "Stop bit" of the serial port must be configured the same as
those of the corresponding device, so as to ensure normal communication
between Logger4000 and the device.
When "PLC Access” corresponding to COM1~COM7 is set to "Enable", the
baud rates of COM1~COM7 will be automatically changed to 115200. And
then MPLC node parameters can be set, referring to
.
-- -- E
En
nd
d
User Manual