14
SPARC T3-1B Server Module Service Manual • July 2012
■
Repaired fault
– When a fault is repaired by human intervention, such as a FRU
replacement, the SP will usually detect the repair automatically and extinguish the
Service Action Required LED. If the SP does not perform these actions, you must
perform these tasks manually by setting the Oracle ILOM
component_state
or
fault_state
of the faulted component. The procedure for clearing faults
manually is described in
“Clear Faults (clear_fault_action Property)” on page 21
Many environmental faults can automatically recover. For example, a temporary
condition might cause the computer room temperature to rise above the maximum
threshold, producing an overtemperature fault in the server module. If the computer
room temperature then returns to the normal range and the server module’s internal
temperature also drops back to an acceptable level, the SP will detect the new
fault-free condition. The SP will extinguish the Service Action Required LED and
clear the fault state from the FRU PROM.
The SP can automatically detect when a FRU is removed. In many cases, the SP does
this even if you remove the FRU while the SP is not running (for example, if you
unplug the system power cables during service procedures). This function enables
Oracle ILOM to sense that a fault, diagnosed to a specific FRU, has been repaired.
Note –
Oracle ILOM does not automatically detect hard drive replacement.
Oracle Solaris Fault Manager Commands in Oracle ILOM
The Oracle ILOM CLI includes a feature that enables you to access Oracle Solaris
fault manager commands, such as
fmadm
,
fmdump
, and
fmstat
, from within the
Oracle ILOM shell. This feature is referred to as the Oracle ILOM
faultmgmt
shell.
HDD Faults
The Oracle Solaris PSH technology does not monitor hard drives for faults. As a
result, the SP does not recognize hard drive faults and will not light the fault LEDs
on either the server module or the hard drive itself. Use the Oracle Solaris message
files to view hard drive faults. See
“View the System Message Log Files” on page 24
Related Information
■
Oracle Integrated Lights Out Manager (ILOM) 3.0 Concepts Guide
■
SPARC T3 Series Servers Administration Guide
■
“Oracle ILOM Troubleshooting Overview” on page 12
■
Содержание Netra SPARC T3-1B
Страница 1: ...SPARC T3 1B Server Module Service Manual Part No E29280 02 July 2012 ...
Страница 7: ...Contents vii Start the Server Module Host 114 Glossary 115 Index 121 ...
Страница 8: ...viii SPARC T3 1B Server Module Service Manual July 2012 ...
Страница 12: ...xii SPARC T3 1B Server Module Service Manual July 2012 ...
Страница 100: ...88 SPARC T3 1B Server Module Service Manual July 2012 Related Information Remove a REM on page 85 ...
Страница 116: ...104 SPARC T3 1B Server Module Service Manual July 2012 ...
Страница 131: ...Glossary 119 W WWID World wide identifier A unique number that identifies a SAS target ...
Страница 132: ...120 SPARC T3 1B Server Module Service Manual July 2012 ...