4-2
SPARCcenter™ 2000/2000E Installation Manual—June 1996
4
Figure 4-1
Key Switch Positions
c. Verify that the cabinet AC power cord is plugged into a wall socket.
Caution – The outlet must be a 200-240 Vac 30-ampere circuit intended solely
for use by the server cabinet. The electrical receptacles must be grounded, and
the grounding conductors serving these receptacles must be connected to the
earth ground at the service equipment.
Caution – Do not disconnect the AC power cord from the wall socket when
you work on or in the server cabinet. This connection provides a ground path
that prevents damage from electrostatic discharge.
Warning – Never move the system or expansion cabinets when system power
is on. Excessive movement can cause catastrophic disk drive failure. Always
power the system OFF before moving it.
2. Turn on power to any expansion cabinets.
Read the documentation supplied with each type of expansion cabinet for
specific instructions.
Standby
On
Diagnostics
Secure
!
!
!