![Sun Microsystems SPARCcenter 2000 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/sun-microsystems/sparccenter-2000/sparccenter-2000_installation-manual_1392453022.webp)
1-8
SPARCcenter™ 2000/2000E Installation Manual—June 1996
1
1.5.3 Environmental Requirements
Table 1-7
Temperature Limits
Operating
1
1. The 1/2-inch front load tape drive has a maximum temperature limit of 86
°
F (30
°
C).
Non-operating
U.S.
Metric
U.S.
Metric
Recommended range
50
°
- 104
°
F
10
°
- 40
°
C
–4
°
- 140
°
F
–20
°
- 60
°
C
Minimum temperature
50
°
F at 20% RH
10
°
C at 20% RH
–4
°
F
–20
°
C
Maximum temperature
104°
F at 20% RH
40
°
C at 20% RH
140°
F
60
°
C
Maximum gradient
<27
°
F/hr <30% RH/hr
<15
°
C/hr <30% RH/hr
<27
°
F/hr <30% RH/hr
<15
°
C/hr <30%
RH/hr
Dwell at extremes
8 hours
8 hours
24 hours
24 hours
Table 1-8
Humidity Limits
Operating
Non-operating
U.S.
Metric
U.S.
Metric
Recommended range
5% to 95% RH at 104
°
F
5% to 95% RH at 40
°
C
5% to 95% RH at 104
°
F
5% to 95% RH at 40
°
C
Minimum humidity
5%
5%
5%
5%
With tape drive
20%
Maximum humidity
95%
95%
95%
95%
With tape drive
80%
Maximum gradient
<30% RH/hr <27
°
F/hr
<30% RH/hr
<15
°
C/hr
<30% RH/hr <18
°
F/hr
<30% RH/hr
<10
°
C/hr
Dwell at extremes
8 hours
8 hours
120 hours
120 hours
Содержание SPARCcenter 2000
Страница 8: ...viii SPARCcenter 2000 2000E Installation Manual June 1996 ...
Страница 14: ...xiv SPARCcenter 2000 2000E Installation Manual June 1996 ...
Страница 28: ...1 14 SPARCcenter 2000 2000E Installation Manual June 1996 1 ...
Страница 54: ...Index 4 SPARCcenter 2000 2000E Installation Manual June 1996 ...