62
Netra ft 1800 Installation Guide • February 1999
You must leave two free slices for Sun StorEdge Volume Manager. The disk layout
should have a maximum of five slices, plus the overlap slice, similar to the
following:
There will be some rounding differences.
You must also leave 1024 sectors, or 512K, free for Sun StorEdge Volume Manager
within the total space available. This space is required for the allocation of an on-
disk database to allow the disk to be encapsulated. See the Sun StorEdge
Volume Manager Release Notes for full details.
6. Select Manual Reboot.
7. After Solaris has finished booting, set the default boot device:
This sets the boot device to the disk in location
A-DSK0
. If you installed on a disk
drive in a different location, replace
a-dsk0
with the location that corresponds to
the default device that you set during Solaris installation.
8. Re-engage the HDD modules which you removed before installation, and remove
the CD from the drive if you installed locally.
Eject the CD using
vold
.
9. Reboot the system by typing:
A few minutes after the system has rebooted to the system prompt, the Sync LEDs
on the CPUsets will illuminate and remain steadily lit, indicating that the system is
now running in synchronization.
TABLE 5-1
Suggested Disk Layout
Slice
Size
/
3000
swap
512 (rounds up to 513)
overlap
no change
/export
2000
/opt
2000
/var
1050
# eeprom boot-device=a-dsk0 diag-device=a-dsk0
# reboot
Содержание Netra ft 1800
Страница 6: ...vi Netra ft 1800 Installation Guide February 1999 ...
Страница 10: ...x Netra ft 1800 Installation Guide February 1999 ...
Страница 40: ...26 Netra ft 1800 Installation Guide February 1999 FIGURE 2 12 Removing a CPUset Module ...
Страница 41: ...Chapter 2 Hardware Installation 27 CAF Modules FIGURE 2 13 Removing a CAF ...
Страница 42: ...28 Netra ft 1800 Installation Guide February 1999 PCI Modules FIGURE 2 14 Removing a PCI Card Carrier ...
Страница 43: ...Chapter 2 Hardware Installation 29 PSU Modules FIGURE 2 15 Removing a Power Supply ...
Страница 45: ...Chapter 2 Hardware Installation 31 FIGURE 2 16 Removing an RMM Module ...
Страница 56: ...42 Netra ft 1800 Installation Guide February 1999 ...
Страница 90: ...76 Netra ft 1800 Installation Guide February 1999 W weight empty chassis 6 maximum 2 removable modules 6 ...