CONTROL PANEL SULZER APC 1/2B 

 USER GUIDE 

Rev.13  (2018/08/30) 

 
- PC 242 enables advanced management of pumping "INPUT FLOW CALCULATION". Based on level 
measurement and analogue sensor data entered into during the launch of the volume of the well, the 

system accurately calculates the flow rate into the well when the pumps are stopped. It is very difficult 
to implement this feature when the water inlet manifold is at levels close to the bottom of the well. 
 

- PC 242 enables advanced management of pumping "CALCULATING THE CAPACITY OF BOMBS". 
Based on the input flow and knowing that does not change abruptly whenever one starts a pump, PC 
242 estimated pumping capacity running an advanced calculation algorithm based on interpolation 

between input and output flows. 
 
- PC 242 enables advanced management of pumping "OUT FLOW CALCULATION". Based on the 

calculated value for the pumping capacity of each pump, PC 242 can meet the outflow both when only 
one pump is running, as when several work at once (using a correction factor of pumps in parallel). 
 

- PC 242 enables advanced management of pumping "DYNAMIC MONITORING WELL". Thanks to its 
colour LCD graphic display, PC 242 displayed dynamically and numerical levels, consumption of 
pumps and pumping flow rates as well as numerically the pump status, alarm signals, historical 

operating and alarms, etc. Connect the signal cables box of each pump and level measuring element 
to make better use and management of pump alarms and in this way work with PC 242 pump vital 
signs (temperature sensors and humidity, state motor protection circuit breaker, motor consumption or 

contactor activation confirmation gear pumps) and pump (level sensor and / or operating buoys and 
buoy alarm). In standard execution level sensor allows monitoring APC1/2B level, flow, and 
consumption in amps, to include power module option: active, reactive and apparent power, power 

factor loads, mains voltage, etc.. PC 242 also allows you to trend graphs level curves, consumption 
and flow pumping. 
 

- PC 242 enables advanced management of start and stop pumping before abrupt change in level, 
function known as "START EARLY IN CASE OF STORM". It is able to start the pumps in advance to 
avoid overflows in the well if it detects sudden changes in level. In rainwater pumps and pumping 

sewage mixed is easier than to start a storm wells filling up the dimensions will start pumping when the 
bombs begin to start flooding these wells are finished without a good relationship between storage 
volume and pump capacity and collector wells receiving water from other pumps. Start function level to 

abrupt change allows to anticipate this situation and start the pumps prior to reaching the normal 
working levels (if the level is above the elevation of unemployment), so that the water will start to 
evacuate beforehand, preventing overflow and laminating the water inlet to the treatment plant. 

 
- PC 242 enables advanced management of pumping up doing short cycles, even without water in the 
well, to exercise each pump after long periods without this has worked, such a manoeuvre between 1 

and 10 seconds after 2 or Stop 5 days, depending on the type of fluid in which the pump is submerged, 
and the model and power of the same. It is highly recommended to use this "FEATURE PUMP 
EXERCISE" also known as "DRY SEASON START" mainly in storm water pumping so as to avoid 

blocking the pump shaft by oxidation. 
  
- PC 242 Advanced manages pumping with "RANDOM STRIP DIMENSIONS REFERRED TO RUN". 

From the PC 242 user interface for each pump adjust band randomly around the dimension you've set 
for March, so that the pump starts randomly when the level is in the range of dimensions defined by the 
height of up + / - random band said. The feature is only available to work with analogue level sensor, 

not buoys, and is useful for preventing the formation of crust (and the resulting odours) regrowth on the 
walls of the well at elevation where the first bomb usually tear. 
 

Содержание ABS APC 1/2B NG

Страница 1: ...nal inscrita en el Registro Mercantil de Madrid Sulzer Pumps Wastewater Spain S A Avda de la Técnica 5 28522 Rivas Vaciamadrid Madrid www sulzer com ABS APC UP TO 1 Ó 2 PUMPS CONTROL PANEL BY SULZER PUMPS WASTEWATER SPAIN S A USER GUIDE ...

Страница 2: ... 2 5 INSTALLATION RECOMMENDATIONS 2 6 CONTROL SYSTEM DESCRIPTION 3 OPERATION 3 1 AUTOMATIC SEQUENCES 3 2 SAFETY FACTORS 4 RECOMMENDED DOCUMENTS FOR READING 4 1 ELECTRICAL DRAWING 4 2 4 2FORM TO REGISTER PC242 SETTINGS 4 3 USER GUIDES fOR DEVICES RELATED TO APC CONTROL PANELS A LEVEL SENSORS MD124 MD126 MD127 USER AND INSTALLATION GUIDE B PC242 PUMPS CONTROLLER INSTALLATION GUIDE C PC242 PUMPS CONT...

Страница 3: ... to the electrical net under any circumstances Before doing it make sure the control panel is completely disconnected We recommend you to contact to an authorized specialist company to install the control panel and connect the cables its personnel must known and follow the electrical rules technically and regarding safety and recommendations To avoid loosing the guaranty only Sulzer Pumps Wastewat...

Страница 4: ...ersion and made by relays allowing working even if PC 242 were broken down in APC complete version Ready to receive a thermal sensor signal from each pump that could be bimetallic type PTC or PT100 PC 242 has an internal module to manage PTC and PT100 signals built in what allows to indicating the current temperature the sensor measures and set alarm set points Ready to receive a leakage sensor si...

Страница 5: ... to PE terminal clamp 3 Same way you could see that thermal signal cables from pumps named F0 and F1 must be connected in terminal clamps Bn F0 and Bn F1 and leakage signal cables from pumps named DI and PE must be connected in terminal clamps Bn DI and Bn PE Some small pumps have power and signal wires in the same cable in that case you will not have a PE cable for power and other for signals not...

Страница 6: ...to avoid pipe clogging as making a diagonal cut to the air pipe to have a bigger area of the side of the pipe submersed as it is shown at the left side picture When using an hydrostatic level sensor you must consider effects that could appear when installing the sensor hung from the pump pit top turbulences could make it hit itself with the sump walls or making a pendular movement that will could ...

Страница 7: ...stop if the MCB the earth leakage switch or the thermal sensor were tripped or in case of motor drive failure It is thought mainly for tests during the pump station setting up and maintenance pump checks For safety reason it returns automatically to 0 you have to keep activating the selector for the period of time you want to retain the pump running avoiding to burn the motor by accident PUMP DISA...

Страница 8: ...ES the PC 242 user and installation guides and the document named SETTINGS IN CONTROL PANEL MODEL APC2B COMPLETE PROGRAMMED FOR USING WITH LEVEL FLOATS specific for this project SEMI AUTOMATIC OPERATION SELECTOR IN AUTO APC control panel basic version has a semi automatic control system based on a PC 242 feature that runs the pumps if the high level float gets active what could happen in case of f...

Страница 9: ...one common stop level float to the unit they will stop with a delay between stops See PC 242 user guide and the document named SETTINGS IN CONTROL PANEL MODEL APC2B COMPLETE PROGRAMMED FOR USING WITH LEVEL FLOATS specific for this project for more details or to learn how to change related settings Both starts and stops are done with a delay in between to avoid more than two or more pumps were star...

Страница 10: ... apparent power power factor loads mains voltage etc PC 242 also allows you to trend graphs level curves consumption and flow pumping PC 242 enables advanced management of start and stop pumping before abrupt change in level function known as START EARLY IN CASE OF STORM It is able to start the pumps in advance to avoid overflows in the well if it detects sudden changes in level In rainwater pumps...

Страница 11: ...to work in the highest area of the well pumping more caudal less consumption so you save energy by improving the performance and reducing working hours in addition to extending the life of the pump Also allows us to make emptying the pit to levels even lower than the normal stop before passing the stretch of arrival peak hour flow in order to avoid overflows PC 242 allows REMOTE CONTROL AND PROTEC...

Страница 12: ...used for filling tanks or pumping catchment so that by default the APC box comes with this feature disabled if interested activate follow the user manual PC 242 and or implementation guide APC 2B frame HIGH LEVEL ALARM If you use an APC box with analogue level sensor and also shows the sump level in real time via the display in both graphical and numerical mode PC 242 allows you to generate alarms...

Страница 13: ...oating contact general fault This alarm also for pumps and also signalled only helps the user PUMP NOT IN AUTO NOT AVAILABLE Each pump has a switch MAN AUT 0 in front of the box to set the operating mode in which we work If after handling is left in position 0 the pump is out of service To avoid this if after 60s the selector is not passed to AUTO PC 242 advised of this fact by an alarm text not i...

Страница 14: ...of using general differential protection frame header used motor output protection to ensure the availability of pumps in pumping since in case of tripping earth leakage current in a pump or the feed cable or against nuisance tripping on start would act only protecting the pump leaving the rest available thus differential protection is especially important in pumping rainwater Fully finished in AP...

Страница 15: ...ailure of motor control element a driver may drop etc CRITIC ALARM ALL PUMPS BLOCKED If a pump is blocked by PC242 due to an alarm or switch MAN AUT 0 to 0 and for some reason it blocks the other pump pumping out of service will be completely automatic To indicate this after some time of 30s PC242 generate an alarm by the alarm text B1 and B2 blocked We can consider this alarm criticism for any pu...

Страница 16: ...APC that allows you to indicate if you want this system to act only with the pump B1 B2 with the pump or with both Once activated the alarm float pilot box excite alarm for warning buoy 2KA0 alarm and relay starting the pumps enabled it ie those selected with the selector 2S4 called SEMI COMPLETE APC and the operating mode selector to AUT Pump In Tables 23A over 2TIM1 timer is used to prevent acti...

Страница 17: ...ee contacts for remote signalling 1 alarm per pump and 1 to indicate that PC 242 has an alarm s pending reset This can be seen easily in the extract of the wiring diagram in the following figure APC offers power output buzzer light alarm ABS 9000056 or similar As you can see in the figure above connect the warning signal or you can use the floating signal is desired along with the terminals AL and...

Страница 18: ...G 4 1 ELECTRICAL DRAWING 4 2 FORM TO REGISTER PC242 SETTINGS 4 3 USER GUIDES FOR DEVICES RELATED TO APC CONTROL PANELS A LEVEL SENSORS MD124 MD126 MD127 USER AND INSTALLATION GUIDE B PC242 PUMP CONTROLLER INSTALLATION GUIDE C PC242 PUMP CONTROLLER USER GUIDE D PC242 PUMP CONTROLLER COMLI MODBUS REGISTER GUIDE ...

Страница 19: ...l with references 84004263 84004264 84004265 84004266 84004307 84004308 84004511 84004512 84004513 84004514 84004515 84004516 84004517 84004518 84004519 84004520 84004521 84004522 84004523 84004524 To which this declaration relates are in conformity with the following standards or other normative documents IEC 158 1 2 IEC 364 1 7 IEC 255 1 IEC 408 IEC 337 1 IEC 204 1 2 IEC 158 IEC 292 CE 73 23 CE ...

Отзывы: