WALL SLEEVE AND GRILLE INSTALLATION

Refer to installation instructions included with the wall sleeve kit for 

guidance in assembling and installing the wall sleeve and grille.

CAUTION:

 The sleeve will support the back of the unit.

VENTING

The Dynapack unit uses outside air for combustion and vents the 

exhaust products directly outside.  The Dynapack unit cannot be vented 

with other appliances.  The venting system of the Dynapack unit cannot 

be modified or adjusted in any manner other than what is specified in 

these instructions.

The installation must be planned before hand so that the unit exhaust 

vent location complies with local or national codes in regards to 

distances between the unit vent and doors, operable windows, side 

walks, balconies, and patios.  See the National Fuel Gas Code Z223.1 

for the USA or Installation Code CANI-B149 for Canada.  See Figure 8.

The Dynapack unit contains an adjustable vent.  The vent must be adjusted 

based on the wall sleeve used for proper operation.  See figure 2.

The Dynapack unit venting system is certified to operate at wind speeds 

up to 40 miles per hour. 

VENT PIPE ADJUSTMENT

The vent pipe must be adjusted to match the depth of the wall sleeve.  

CAUTION:

  Failure to properly adjust the vent can lead to exhaust 

recirculation and poor combustion.

1.

  The vent pipe adjustment is accessible from the condenser air 

discharge portion of the unit.  The retaining screw for the vent pipe 

is located to the right of the condenser fan.

2.

  Remove and retain the #10 sheet metal screw which attaches the 

vent pipe to its mounting bracket.  See figure 2.

3.

  The vent extension tube contains six holes, each of which is 

intended for a particular wall sleeve depth.  Use table 1 and figure 

2 to select the proper mounting hole for the vent extension tube.  

4.

  Reinstall the #10 sheet metal screw to secure the vent extension 

tube and exhaust tube to its mounting bracket. 

DETERMINING HOLE SETTING

Wall Sleeve Stock 

Number

Hole #

Approximate Length 

the Vent Extends from 

the Cabinet

1736 or 1741

A

3

/

8

 inches

1737 or 1742

B

3

/

8

 inches

1738 or 1743

C

3

/

inches

1739 or 1744

D

10 

3

/

8

 inches

1740 or 1745

E

12 

3

/

8

 inches

TABLE 1

INSTALLATION

WARNING!

 

Installation of this appliance must be made in accordance with the written 

instructions provided in this manual. No agent, representative or employee of Suburban or 

other person has the authority to change, modify or waive any provision of the instructions 

contained in this manual.

The  Dynapack  units  are  vertical  package  units  featuring  gas  fired 

heating with electrical air conditioning.   The Dynapack unit has been 

safety certified by Intertek Testing Services to comply with the national 

safety codes of the USA and Canada.  The Dynapack unit is certified to 

operate on natural or LP gas.

The  Dynapack  unit  is  NOT  certified  for  installation  in  a  mobile 

home.

Installations in the USA must be in accordance with city, county, or state 

codes and regulations.  If local codes do not apply then the installation 

must be made in accordance with the National Fuel Gas Code and the 

National Electrical Code. 

Installations made in Canada likewise must be in accordance with 

city, provincial, or national codes or the current version of CANI-B149 

Installation Code.

WARNING!

 

In the state of Massachusetts: This product must be installed by a licensed 

Plumber or Gas Fitter.  When flexible connectors are used, the maximum length shall not 

exceed 36".  When lever-type gas shutoffs are used, they shall be T-handle type.

The outdoor fan discharge or the condenser air intake cannot be 

connected to field fabricated ducting.  This unit can only be installed 

using the factory supplied wall sleeves.

LOCATION

IMPORTANT:

 

The Dynapack condensate drain system is designed to be installed in a 

conditioned space. To prevent freezing of the drain condensate in the P-Trap, the installation 

location should not be exposed to freezing conditions. In installations where the drain system 

is exposed to freezing conditions, we offer an optional heated P-Trap which is available for 

purchase. The part number for the heated P-Trap installation kit is K/10348

 and the steps for 

installation are outlined in Appendix A. 

The Dynapack unit is approved for indoor installation only and must 

be installed with one of the factory supplied wall sleeves.  The unit is 

intended to be installed in a closet or equipment room.  The unit is 

certified  for  0”  clearance  to  the  cabinet  sides,  cabinet  back  and  the 

first 3 feet of the supply duct.  However for accessibility reasons it is 

recommended to maintain at least 1” clearance on the sides for proper 

installation  and  servicing.    For  closet  installations  allow  4”  clearance 

from the unit door panels to the closet door.  For equipment room 

installations allow 24”clearance from the unit door panels to a wall for 

servicing.

The  wall  sleeve  and  grille  is  intended  to  be  installed  flush  with  the 

exterior wall.  The unit, wall sleeve, and grille are required to be 

installed certain distances from adjacent doors, operable windows and 

shrubbery.  See figure 8.

CAUTION:

 The unit must be installed level front to back and side to 

side.  Adjust front leveling legs as necessary.

TOP VIEW

4" MIN. TO DOOR

1" RECOMMENDED

1" RECOMMENDED

CONTROL WIRES

ELECTRICAL POWER

Figure 1

A

B

C

D

SHIPPING POSITION

POSITION

NOMINAL 

WALL SLEEVE 

DEPTH

A

B

C

D

E

5 7/8"

7 7/8"

9 7/8"

11 7/8"

13 7/8"

E

Figure 2

2

Содержание DYNAPACK S Series

Страница 1: ...the National Safe Transit Test This means that the packaged product with normal handling will withstand the load conditions encountered in normal transit and in handling Your unit should be inspected...

Страница 2: ...ack unit has been safety certified by Intertek Testing Services to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural or LP gas The Dynapa...

Страница 3: ...y out side or turned inside and routed to the building drain system If the wall sleeve drain is routed to the building sewer system then it must be trapped to prevent sewer gasses from escaping ELECTR...

Страница 4: ...is recommended that a 5 conductor thermostat wire be used in case the room thermostat needs power from the unit transformer The low voltage pigtails for the thermostat wiring must be routed to the ou...

Страница 5: ...at will call for heat and the combustion blower will begin to operate 6 The combustion blower will operate for 15 to 20 seconds before the ignition controls begins sparking then the gas valve will ope...

Страница 6: ...tion for both the USA and Canada Call Technical Service at 423 775 2131 for installations above 4500 feet OPERATION IN EXTREME COLD OR SNOWY AREAS In those areas where the ambient temperature is consi...

Страница 7: ...le Bronze Finish DYPA30AC1A and DYPA36AC1A 521051 LP Conversion Kit All Models 36 000 BTU input 48 000 BTU input 60 000 BTU input 1741 5 7 8 Wall Sleeve Kit DYPA12 DYPA18 and DYPA24 1736 5 7 8 Wall Sl...

Страница 8: ...G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O NOTE 1 Y BK PK BL BL LIMIT BLOWER R O...

Страница 9: ...3m a D VERTICAL CLEARANCE TO VENTILATED SOFFIT LOCATED ABOVE THE TERMINAL WITHIN A HORIZONTAL DISTANCE OF 2 FEET 61cm FROM THE CENTER LINE OF THE TERMINAL a a M CLEARANCE UNDER VERANDA PORCH DECK OR B...

Страница 10: ...sponsibility and liability of the owner An owner requesting performance under this Warranty shall provide reasonable access to the allegedly defective or malfunctioning product or part to Airxcel Comm...

Страница 11: ...ng wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 Insert...

Страница 12: ...iphon en T dans le tuyau de drainage en caoutchouc L utilisation d eau savonneuse peut faciliter l insertion 10 Alignez le siphon en P selon le besoin par rapport la plomberie de drainage existante 11...

Страница 13: ...n tel service seront assum s par le demandeur Un propri taire requ rant une intervention ce titre dans le cadre de la garantie devra permettre un acc s raisonnable au produit ou la pi ce incrimin e po...

Страница 14: ...ITU ES SUR DES PROPRI T S PUBLIQUES 7 PIEDS 2 13 cm a D ESPACE LIBRE LA VERTICALE PAR RAPPORT AU PAREMENT VENTIL SITU AU DESSUS DE LA SORTIE a a M ESPACE LIBRE SOUS LES V RANDAS LES PROCHES LES PATIOS...

Страница 15: ...L ALLUMEUR CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAMME 24V FLAMME INTERRUPTEUR BL O 230V INDUCER BK R OFM C BK BR WHT VANNE GAZ FIN DE COURSE HAUTE PRESSOSTAT INTERRUPTEUR MISE EN APPLICATION O...

Страница 16: ...DYPA36AC1A 521051 Trousse de conversion au GPL tous les mod les Entr e de 36 000 BTU entr e de 48 000 BTU et entr e de 60 000 BTU 1741 Support mural de 5 7 8 po DYPA12 DYPA18 and DYPA24 1736 Support...

Страница 17: ...nt un but particulier et il ne faut pas les trafiquer en changeant leur emplacement ou par un c blage sp cial Si la fournaise ne fonctionne pas si le ventilateur de l air ambiant ne se met pas en marc...

Страница 18: ...z l appareil sous tension 3 Placez le thermostat de la pi ce en position de chauffage 4 Augmentez le r glage au dessus de la temp rature ambiante 5 Le thermostat demandera du chauffage et le ventilate...

Страница 19: ...de l appareil doit tre v rifi Ne d passez pas lb po ca de pression manom trique ou 14 po CE pour ce test autrement la vanne gaz pourrait tre endommag e MISE EN GARDE Suburban ne recommande pas d utili...

Страница 20: ...ou d entretien ALIMENTATION EN GAZ Tous les appareils Dynapack sont con us pour utiliser du gaz naturel L appareil doit tre converti au GPL l aide la trousse de conversion du fabricant si l appareil d...

Страница 21: ...ons pr sent es dans ce manuel Les appareils Dynapack sont des ensembles verticaux contenant un chauffage au gaz et une climatisation l lectricit Les appareils Dynapack sont certifi s au plan de la s c...

Страница 22: ...stall uniquement l aide des accessoires approuv s grille d ext rieur et manchons muraux Le non respect de ces instructions peut entra ner des dommages mat riels des blessures et m me la mort MISE EN G...

Отзывы: