Parameter setting method

Description of parameters and functions.

Parameter

P5
Parameter

Use UP/DOWN keys to set desired 
value. 

Example 

In time it may be possible that the 

display may be offset by a degree or so.
To compensate for this error, you may 
need to add or minus the degrees 
required to achieve the correct 
temperature. 

The temperature on the 

O

display is 28.0 C, whereas the actual 

O

temperature is 30.0 C. You will need to 

O

set this parameter to 2.0 C, which 
means that once out of the programming 
parameter, the display will show the 

O

O

O

temperature 30.0 C (28.0 C + 2.0 C).

To change P5 
press the set key.

parameter, 

05

Function: To set  probe calibration.

-10.0ºC

10.0ºC

0.0ºC

Range

Min

Max

Fact. Set 

P6
Parameter

Use UP/DOWN keys to set desired value. 

Example 

This parameter is used to protect the fan 
from  restarting  in  a  short  period  of  time 
and can be set between 0 to 20 minutes.

 If this parameter is set at 3 

minutes, the compressor will cut off at 
the set temperature, but will not restart 
for a minimum of 3 minutes, even if the 
differential is achieved earlier. This 

To change P6 
press the set key.

parameter, 

06

Function : To set time delay between 
relay restart time.

1 Min

20 Min

3 Min

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired value.

Example(Cooling Mode) : 

 If the set 

0

point is set at 10.0 C and differential is  

0

set at 2.0 C, then when the  system 

0

reaches 10.0 C, the  comp. relay will 

0

cutout. Since the differential is 2.0 C, the 

0

comp. Relay will cutin at 12.0 C

0

0

(10.0 C + 2.0 C).  

04

P4
Parameter

Function: To set the differential for 
compressor restart. 

To change 

P4 

press the set key.

parameter, 

0.5ºC

20.0ºC

2.0ºC

Range

Min

Max

Fact. Set 

08

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

P7
Parameter

07

Function : To set duration of defrost.

To change the P7 Parameter, 
press the set key.

Use UP/DOWN keys to set desired value. 

0 Min

99 Min

30 Min

Range

Min

Max

Fact. Set 

This is maximum amount of time allowed 
for  defrost.  If  set  to  0,  there  will  be  no 
defrost cycle

Example :

 If P7 is set to 30 Mins and 

P8 parameter is set to 1 Hr. then after 
every 1 Hr defrosting will take place for 
30 mins. In defrosting Compressor , 
Evap Fan relay willl be OFF.

P8
Parameter

08

Function : To set defrost frequency.

To change the P8 Parameter, 
press the set key.

Use UP/DOWN keys to set desired value. 

1 Hrs

31 Hrs

6 Hrs

Range

Min

Max

Fact. Set 

This is the amount of time between two 
defrost cycles.  

Example : 

same as P7 parameter. 

P9
Parameter

09

Function : To set power on defrost delay.

To change the P9 Parameter 
parameter, press the set key.

Use UP/DOWN keys to set desired value. 

0 Min

99 Min

30 Min

Range

Min

Max

Fact. Set 

This  is  the  amount  of  time  at  power  on 
after  which  defrosting  will  take  place 
once.

Example : 

If P9 parameter is 30 mins 

then at power after 30 mins defrosting 
will take place once.

parameter is good to protect the life of 
the compressor when there are power 
fluctuations and the compressor is 
switched off and on within a few seconds. 

Содержание CRC-1001

Страница 1: ...COLD ROOM CONTROLLER USER MANUAL www ascontrols com INDIA CRC 1001 CRC 1001 C...

Страница 2: ...Under current limit UL 10 11 Key Introduction 5 To set Current sensing delay C2 11 D0 To enable or Disable HP sensing 12 3 Main Programming Mode 5 Suggested wiring diagram for CRC 1001 C To enable or...

Страница 3: ...ety features which include shutting down the system incase of a fault from a pressure control or similar device Aseries of safety controls delay at start up minimum disable time minimum time between a...

Страница 4: ...ll show HT High Temperature The alarm will be ON But at power on till the AL delay is over controller will not generate HTAlarm Once set at a particular value this will not allow the set point to go a...

Страница 5: ...he comp relay will 0 cutout Since the differential is 2 0 C the 0 comp Relay will cutin at 12 0 C 0 0 10 0 C 2 0 C 04 P4 Parameter Function To set the differential for compressor restart To change P4...

Страница 6: ...t will show OV fault on display and Compressor Relay will be off V1 Parameter 15 Function To set time delay for voltage sensing To change the V1 Parameter parameter press the set key Use UP DOWN keys...

Страница 7: ...ample If C2 parameter is 1 Sec then any current fault will be valid only when it exsists for more than 1 sec 0 Sec 60 Sec 5 Sec Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter setting me...

Страница 8: ...TEMP DEF TEMP Range Min Max Fact Set Range Min Max Fact Set OFF ON ON E3 Parameter Use UP DOWN keys to set desired value OFF Heater will stay Off ON Heater will stay On at compressor off condition Cr...

Страница 9: ...act Set 16 Sr No Parameter setting method Description of parameters and functions Parameter KEYPAD LOCK 34 To change Keypad Lock parameter press the set key NO YES NO Function To activate Keypad Lock...

Страница 10: ...70 C non condensing Output Compressor Relay 20A 250Vac Evap Relay 10 3 A 250Vac Crankcase Heater 8 2 A 250Vac Light Relay 5A 250Vac Alarm Relay 5A 250Vac Input 1 NTC Probe 0 0 Range 50 0 C to 50 0 C 0...

Страница 11: ...250VAC 20Amax CCH or Contactor Coil 250VAC 8 2 Amax Evap or Contactor Coil 250VAC 10 3 Amax 20 Suggested wiring Diagram for CRC 1001 C 20 21 22 230V N L Caution Wiring for 230Vac Load Only 2 1 PHASE...

Страница 12: ...ch damages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents r...

Страница 13: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Отзывы: