Parameter

17

Function : To set Over current limit.

To change the OL parameter, 
press the set key.

Use UP/DOWN keys to set desired 
value.

This parameter used to switch off the 
compressor incase it draws higher 
current than the set current. 

Example :

 If this parameter is set at 

10.0A, the controller will trip compressor 
if it draws more than 10.0A.Controller 
will restart the compressor after the set
time delay. If after 3 retries within 1hour, 
current drawn is still more than 10.0A, 
the controller will trip the compressor on 
fault and activate the respective alarm 
relay. Also display will flash “OL”.

(UL+1.0)A

18.0A

10.0A

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired value.

Example : 

ENB = HP sensing is enabled.
DIS   = HP sensing is disabled

If this parameter is set to

Setting this parameter to disable will 
ignore HP fault for compressor. If this 
parameter is set to Enable then controller 
will detect HP trip. 

To change the D0 parameter, 
press the set key.

D0
Parameter

19

Function  :  To  enable  or  Disable  HP 
sensing. 

DIS 

ENB

ENB

Range

Min

Max

Fact. Set 

To change the C2 parameter, 
press the set key.

C2
Parameter

18

Function: To set Current sensing delay.

Use UP/DOWN keys to set desired 
value.

Example : 

If C2 parameter is 1 Sec 

then, any current fault will be valid only 
when it exsists for more than 1 sec.

0 Sec

60 Sec

5 Sec

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

D2
Parameter

21

To change D2 parameter, 
press the set key.

0V

230V

Function: To set fault sensing logic.

230V

Use UP/DOWN keys to set desired 
value.

0v = 

rip the 

compressor.

230V = 

rip the 

    compressor.

          

 0V at HP/LP/AUX input will be 

sensed as fault and t

 230V at HP/LP/AUX input will be 

    sensed as fault and t

Range

Min

Max

Fact. Set 

Example : 

I

f this parameter is set at 

1.0A, the controller will trip compressor if 
it draws less than 1.0A. Controller will 
restart the compressor after the set time 
delay. If after 3 retries within 1hour, 
current drawn is still less than 1.0A, the 
controller will trip the compressor on fault 
and activate the respective alarm relay. 
Also display will flash “UL”.

Use UP/DOWN keys to set desired 
value.

Example:  

If this parameter is set to 
ENB = LP sensing is enabled.
DIS   = LP sensing is disabled.
Setting this parameter to disable will 
ignore LP fault for compressor. If this 
parameter is set to Enable then controller 
will detect LP trip. 

To change D1
parameter, press the set key.

DIS 

ENB

D1 
Parameter

20

ENB

Function: To enable or disable LP 
sensing.

Range

Min

Max

Fact. Set 

Содержание CRC-1001

Страница 1: ...COLD ROOM CONTROLLER USER MANUAL www ascontrols com INDIA CRC 1001 CRC 1001 C...

Страница 2: ...Under current limit UL 10 11 Key Introduction 5 To set Current sensing delay C2 11 D0 To enable or Disable HP sensing 12 3 Main Programming Mode 5 Suggested wiring diagram for CRC 1001 C To enable or...

Страница 3: ...ety features which include shutting down the system incase of a fault from a pressure control or similar device Aseries of safety controls delay at start up minimum disable time minimum time between a...

Страница 4: ...ll show HT High Temperature The alarm will be ON But at power on till the AL delay is over controller will not generate HTAlarm Once set at a particular value this will not allow the set point to go a...

Страница 5: ...he comp relay will 0 cutout Since the differential is 2 0 C the 0 comp Relay will cutin at 12 0 C 0 0 10 0 C 2 0 C 04 P4 Parameter Function To set the differential for compressor restart To change P4...

Страница 6: ...t will show OV fault on display and Compressor Relay will be off V1 Parameter 15 Function To set time delay for voltage sensing To change the V1 Parameter parameter press the set key Use UP DOWN keys...

Страница 7: ...ample If C2 parameter is 1 Sec then any current fault will be valid only when it exsists for more than 1 sec 0 Sec 60 Sec 5 Sec Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter setting me...

Страница 8: ...TEMP DEF TEMP Range Min Max Fact Set Range Min Max Fact Set OFF ON ON E3 Parameter Use UP DOWN keys to set desired value OFF Heater will stay Off ON Heater will stay On at compressor off condition Cr...

Страница 9: ...act Set 16 Sr No Parameter setting method Description of parameters and functions Parameter KEYPAD LOCK 34 To change Keypad Lock parameter press the set key NO YES NO Function To activate Keypad Lock...

Страница 10: ...70 C non condensing Output Compressor Relay 20A 250Vac Evap Relay 10 3 A 250Vac Crankcase Heater 8 2 A 250Vac Light Relay 5A 250Vac Alarm Relay 5A 250Vac Input 1 NTC Probe 0 0 Range 50 0 C to 50 0 C 0...

Страница 11: ...250VAC 20Amax CCH or Contactor Coil 250VAC 8 2 Amax Evap or Contactor Coil 250VAC 10 3 Amax 20 Suggested wiring Diagram for CRC 1001 C 20 21 22 230V N L Caution Wiring for 230Vac Load Only 2 1 PHASE...

Страница 12: ...ch damages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents r...

Страница 13: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Отзывы: