13

14

To change E1 parameter, 
press the set key.

E1
Parameter

24

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

When set to 
ON = Relay will stay ON. 
CYC = Relay performs a duty cycle of
           10 minutes ON and  
           4minutes OFF. 
OFF = Relay will stay OFF.

ON

OFF

CYC

Function : To set Compressor Relay 
status on Probe Failure.

Use UP/DOWN keys to set desired 
value. 

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

To change D4 parameter, 
press the set key.

D4
Parameter

23

Function : To set  reset mode for HP fault.

MAN

AUTO

MAN

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired 
value.

MAN = Manual Mode
AUTO = Auto mode

If this parameter set to “MAN” mode HP 
fault will be cleared only after pressing 
reset key for 2 seconds. 
If this parameter is set to “AUTO” mode 
HP fault will be cleared automatically 
when it is healthy.  

E7
Parameter

Use UP/DOWN keys to set desired 
value. 

TEMP = At defrosting temperature
             will be dispalyed.           
DEF = At Defrosting 'Defrost ON' 
            will scroll.

28

Function: To set Display at defrosting.

To change E7 parameter, 
press the SET key.

TEMP

DEF

TEMP

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

OFF

ON

ON

E3
Parameter

Use UP/DOWN keys to set desired 
value. 

OFF = 

Heater will stay Off.

ON = 

Heater will stay On.

at compressor off condition.

Crankcase 

Crankcase 

26

Function : To set Crankcase Heater 
operation when compressor is OFF. 

To change E3 parameter, 
press the set key.

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired 
value. 

OFF = Evap Fan will stay OFF.
ON = Evap Fan will stay ON.
at door open condition.

E4
Parameter

27

Function: To set EVAP Fan operation at 
door open.

To change E4 parameter, 
press the set key.

OFF

ON

ON

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

To change D3 parameter,
press the set key.

0 Sec

22

Min

Min

Use UP/DOWN keys to set desired value.

Example : 

If this parameter is set at 30 

seconds, the system will ignore low 
pressure alarm for 30 sec from 
compressor on. In this manner, a false 
alarm can be avoided due to low 
pressure at compressor start up.

180 Sec

30 Sec

D3
Parameter

Function : To set LP sensing delay.

Range

Max

Fact. Set 

Range

Max

Fact. Set 

E2
Parameter

25

Function : To set Evap fan status when 
compressor is OFF.

Use UP/DOWN keys to set desired 
value. 

OFF = Evaporator Fan will stay OFF. 
ON = Evaporator Fan will stay ON.
at compressor off condition.

To change E2 parameter, 
press the set key.

OFF

ON

ON

Range

Min

Max

Fact. Set 

Range

Min

Max

Fact. Set 

Содержание CRC-1001

Страница 1: ...COLD ROOM CONTROLLER USER MANUAL www ascontrols com INDIA CRC 1001 CRC 1001 C...

Страница 2: ...Under current limit UL 10 11 Key Introduction 5 To set Current sensing delay C2 11 D0 To enable or Disable HP sensing 12 3 Main Programming Mode 5 Suggested wiring diagram for CRC 1001 C To enable or...

Страница 3: ...ety features which include shutting down the system incase of a fault from a pressure control or similar device Aseries of safety controls delay at start up minimum disable time minimum time between a...

Страница 4: ...ll show HT High Temperature The alarm will be ON But at power on till the AL delay is over controller will not generate HTAlarm Once set at a particular value this will not allow the set point to go a...

Страница 5: ...he comp relay will 0 cutout Since the differential is 2 0 C the 0 comp Relay will cutin at 12 0 C 0 0 10 0 C 2 0 C 04 P4 Parameter Function To set the differential for compressor restart To change P4...

Страница 6: ...t will show OV fault on display and Compressor Relay will be off V1 Parameter 15 Function To set time delay for voltage sensing To change the V1 Parameter parameter press the set key Use UP DOWN keys...

Страница 7: ...ample If C2 parameter is 1 Sec then any current fault will be valid only when it exsists for more than 1 sec 0 Sec 60 Sec 5 Sec Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter setting me...

Страница 8: ...TEMP DEF TEMP Range Min Max Fact Set Range Min Max Fact Set OFF ON ON E3 Parameter Use UP DOWN keys to set desired value OFF Heater will stay Off ON Heater will stay On at compressor off condition Cr...

Страница 9: ...act Set 16 Sr No Parameter setting method Description of parameters and functions Parameter KEYPAD LOCK 34 To change Keypad Lock parameter press the set key NO YES NO Function To activate Keypad Lock...

Страница 10: ...70 C non condensing Output Compressor Relay 20A 250Vac Evap Relay 10 3 A 250Vac Crankcase Heater 8 2 A 250Vac Light Relay 5A 250Vac Alarm Relay 5A 250Vac Input 1 NTC Probe 0 0 Range 50 0 C to 50 0 C 0...

Страница 11: ...250VAC 20Amax CCH or Contactor Coil 250VAC 8 2 Amax Evap or Contactor Coil 250VAC 10 3 Amax 20 Suggested wiring Diagram for CRC 1001 C 20 21 22 230V N L Caution Wiring for 230Vac Load Only 2 1 PHASE...

Страница 12: ...ch damages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents r...

Страница 13: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Отзывы: