34
-
© STULZ GmbH, Hamburg
-
34
-
1 - POWER ON
In this phase, which lasts around one second, all the
LEDs on the display light up.
2 - INITIALISATION
This phase lasts 4 seconds. The LEDs shown here
light up on the display.
.
1
2
3
4
5
6
7
8
9
10
11
12
alarm
dehum.
x1000
10
11
6
9
12
2
4
1
3
5
7
8
alarm
dehum.
x1000
alarm
dehum.
x1000
.
1
2
3
4
5
6
7
8
9
10
11
12
alarm
dehum.
x1000
10
11
6
9
12
2
4
1
3
5
7
8
alarm
dehum.
x1000
alarm
dehum.
x1000
n. description
1 button for accessing the most frequent operating parameters (codes Px, dx); also acts as an alarm relay reset button
(if the alarm is no longer active)
2 displays the unit of measure of the value shown on the display; pressed for 2 seconds accesses the display/
programming of the set point; if pressed together with button 1 for 5 seconds, accesses the routine for programming
the configuration parameters
3 when pressed, displays the value measured by the main probe (in ON/OFF control, nothing is displayed); in
programming mode increases the value or moves to the previous parameter
4 when pressed, displays the value measured by the compensation probe (only if featured); in programming mode
decreases the value or moves to the following parameter
5 2
1
/
2
digit display indicating the numeric values and the codes of any alarms in progress; in programming mode
shows the codes of the parameters and their values
6 LED representing the decimal point
7 LED representing that the value indicated on the display should be multiplied by one thousand
8 LED indicating the activation of the dehumidification relays
9 Flashing LED indicating the activation of the alarm relay
10 LED indicating steam production in progress; if flashing, indicates that production is lower than required
11 LED indicating the operation of the fill electrovalve
12 LED indicating the operation of the drain electrovalve
7.3 The humidifier controller
The following type of electric controller is available for the immersed electrode humidifier:
• Type H, with numeric LED display, on/off, proportional or probe-controlled operation.
This type of controller allows the complete control of steam production, including the possibility of activating the dehumidi-
fication function (H configuration); it accepts signals from room probes or external electronic regulators with proportional
or ON/OFF operation.
H controller, with numeric display LED, humidity control operation
7.3.1 Front panel
Fig. 7.3.1.1
Tab. 7.3.1.1
7.3.2 Start-up sequence
When the humidifier is started, the following sequence occurs, as highlighted by the lighting up of the LEDs.
Fig. 7.3.2.1
Fig. 7.3.2.2