![Stulz SupraSteam SEH Series Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/stulz/suprasteam-seh-series/suprasteam-seh-series_manual_1387355049.webp)
-
49
-
© STULZ GmbH, Hamburg
-
49
-
9
11
10
8
12
2
12
5
Fig. 10.2.1B
Fig. 10.2.1C
10.3 Component replacement
10.3.1 Fuses in the auxiliary circuits
Use fuses with the ratings indicated in Table. 10.3.1.1.
model
SEH001 SEH003 SEH005 SEH010 SEH015 SEH 025-45-065
Fuses 1-2 transformer – power supply
1 A, GL, 10.3 x 38 contained in the fuse
carriers on omega rail
Fuse 3 - pump protection
1 A FAST 10.3 x 38 in the fuse
carrier on omega rails
Fuse 4 protection of the secondary
winding
2.5 A T
5 x 20 ceramic
Tab. 10.3.1.1
Note: For the H version board up to 15 kg/h the secondary winding protection is carried out through the thermofuse within
the transformer.
25-35 kg/h
45-65 kg/h