STULZ Ultra-Series Humidifier Controller
54
(August,
2013)
Modbus
TCP/IP
BMS
Address
Modbus
Address
BACnet
Address Description Default
Min
Max
Read/
Write
40044
43
40044
43
Humidifier 15 Temperature (xxx.x°C)
R
40045
44
40045
44
Humidifier 15 Voltage (xx.x volts)
R
40046
45
40046
45
Humidifier 16 Temperature (xxx.x°C)
R
40047
46
40047
46
Humidifier 16 Voltage (xx.x volts)
R
40050 49 40050 49
Dew
Point
Setpoint
R
40051 50 40051 50
Limit
Dewpoint
R
40052
51
40052
51
Limit humidity low alarm point
30.0
R/W
40053 52 40053 52
Limit
temperature high alarm point
80.0
R/W
40054 53 40054 53
Limit
temperature
low
alarm
point
60.0
R/W
40055
54
40055
54
Limit humidity high alarm point
70.0
R/W
40101
100
40101
100
Control temperature high alarm point
80.0
R/W
40102
101 40102
101
Control temperature low alarm point
60.0
R/W
40103
102 40103
102
Control humidity high alarm point
70.0
R/W
40104
103 40104
103
Control humidity low alarm point
30.0
R/W
40105
104 40105
104
dew point Limit Point
72.0
R/W
40106
105 40106
105 Humidity
Limit
Point
80.0 R/W
40107
106 40107
106
Limit high humidity cutout
79.0
R/W
40108 107 40108 107
Limit high humidity cut-in (band is cutout-cut-
in)
75.0 R/W
40109
108 40109
108
Conductivity Pre Alarm limit
5.0
R/W
40110
109 40110
109
Conductivity Alarm limit
20.0
R/W
40111 110 40111 110
Network supplied Contol Humidity set point
/Proportional Control *
R/W
40112
111 40112
111
Network supplied control temperature
R/W
40113 112 40113 112
Network supplied dew point Value (when dew
point configured)
R/W
40114
113 40114
113
Network supplied Limit Temperature Value
R/W
40115
114 40115
114
Network supplied Limit Humidity Value
R/W
40116
115 40116
115
High Airflow Alarm trip point
R/W
40117
116 40117
116
Low Airflow Alarm trip point
R/W
40118
117 40118
117
dew point Control cut-in
-4.0
R/W
40119
118 40119
118
dew point Control cutout
0.0
R/W
40120
119 40120
119
dew point Limit cut-in
-4.0
R/W
40121
120 40121
120
dew point Limit cutout
0.0
R/W
40122
121
40122
121
Network supplied dew point limit
R/W
* If configured for humidity, this is return humidity; if configured proportional, this the percent output
10.2 Unsigned Values for HTTP, SNMP / Modbus Holding Registers / Analog Values for BACnet
Modbus
TCP/IP
BMS
Address
Modbus
Address
BACnet
Address
Description Default
Read/
Write
5002
1
40130
1001
Group A proportional output
R
5003
2
40131
1002
Group B proportional output
R
5004
3
40132
1003
Packed bits for BMS – Alarms 1
R
5005
4
40133
1004
Packed bits for BMS – Alarms 2
R
5006
5
40134
1005
Packed bits for BMS – Humidifier 1 Alarms
R
5007
6
40135
1006
Packed bits for BMS – Humidifier 2 Alarms
R
5008
7
40136
1007
Packed bits for BMS – Humidifier 3 Alarms
R
5009
8
40137
1008
Packed bits for BMS – Humidifier 4 Alarms
R
5010
9
40138
1009
Packed bits for BMS – Humidifier 5 Alarms
R
5011
10
40139
1010
Packed bits for BMS – Humidifier 6 Alarms
R
5012
11
40140
1011
Packed bits for BMS – Humidifier 7 Alarms
R
5013
12
40141
1012
Packed bits for BMS – Humidifier 8 Alarms
R
5014
13
40142
1013
Packed bits for BMS – Humidifier 9 Alarms
R
5015
14
40143
1014
Packed bits for BMS – Humidifier 10 Alarms
R
5016
15
40144
1015
Packed bits for BMS – Humidifier 11 Alarms
R