STULZ Ultra-Series Humidifier Controller
(August, 2013)
35
Humidifier
1
of XX
Coil Overrides
Override Off
Off
Hum Enable Off
Off
Fan Off
Off
Nebulizer Off
Off
Drain Valve Off
Off
Fill Valve Off
Off
Humid
ALARMS
Sensors
1 1/08/2013 10:46
Airflow Alarm
Temperature: 73.0°F
Humidity: 43.7%
Press Alarm to
Clear
Alarms
SENSORS
Options
are useful to STULZ Product Support if technical
assistance is needed. All information is in hexadecimal
(base 16) format.
The first line contains the index into the array of data kept
for all humidifiers, the read value of the coils, the write
value of the coils, and the read value of the discrete inputs.
The second line contains the read voltage, the read status
register, the read value of the temperature and duty cycle
of the nebulizers.
The third line contains the Modbus address of the
humidifier, the voltage calibration value, the configuration
register and the temperature calibration value.
The fourth line contains the maximum fill time, the index
into the register last written, the value last written. The last
word is not used.
The fifth line contains the major revision number, the minor
revision number, the third part of the version number
referred to as the version tweak number, and the clock
tweak value.
5.5.1.14 Manual Control Screen
This screen allows manual control over the coils in the
selected humidifier. The left hand column displays the
current controller On/Off command for the indicated
component, the right hand column is the modifiable field to
change to change the state of the coil. To use this feature,
the Override Coil must be changed to "
On
".
With the Override Coil turned On, manual control of the
listed coils may be turned On or Off. The coils will remain
in the commanded state until the Override Coil is set to
OFF. At that point, the coils revert to normal operations.
NOTE:
On Humidifiers equipped with fans, the fan coil will
automatically be turned on by the humidifier if the
nebulizer coil is turned on.
Alarms
5.5.2
A log of events is stored for view from the Service>Alarms
menu.
SERVICE
This menu is identical to the Alarm Log accessed from the
main menu. It displays the last 50 events sequentially
numbered in order of occurrence. The alarm log may be
erased by pressing the Alarm ( ) key while in this menu.
IMPORTANT NOTE
If the Alarm ( ) key is pressed when in any of the
Service>Alarms screens, all stored alarm
messages will be permanently erased from the
controller's memory.
Sensors
5.5.3
This group of screens allows the setting of an offset to
analog inputs. The offsets are added to the analog input
value for minor corrections of the displayed values.
SERVICE MENU
provided
Alarm History
rovided
SERVICE MENU
provided