STULZ Ultra-Series Humidifier Controller
46
(August,
2013)
Custom Alarm 1
Enable: No
Shutdown: No
Custom Alarm 2
Enable: No
Shutdown: No
Custom Alarm 3
Enable: No
Shutdown: No
Custom Alarm 4
Enable: No
Shutdown: No
Temperature Units: °F
Air Speed: fpm
Change Units? No
Digital
Input
Configuration
5.7.5
This screen allows the enabling of the customer alarm
inputs.
Freeze Alarm, when set to Yes, allows that input to disable
the humidification function.
Group Select, when set to Yes, allows the Group Select
input to determine which Group operates (A or B). This
overrides any auto rotation when set to Yes.
Output
Configuration
5.7.6
The custom alarms can be enabled and can be configured
to shut down the system.
Sensor
Options
5.7.7
This screen allows the enabling of the rest of the analog
sensors.
Measurement
Units
5.7.8
The temperature units may be selected to be °F or °C.
The air speed units may be selected as meters per minute
(m/m) or feet per minute (fpm).
Since this affects many parts of the program, the changing
of the units can only be done by using the Config
password and changing the bottom line from No to Yes. It
will change back to No when it is finished modifying the
system.
Screens Visible Only by Config Password
5.7.9
The following screens appear only when the configuration
password is in effect. They will not appear when any other
password is in effect.
Output Config
Customer Alarm 1: No
Customer Alarm 2: No
Customer Alarm 3: No
Freeze Alarm: No
Group Select: No
Digital Input Config
Output Config
Conductivity: Yes
Limit Temp Sensor: No
Limit Hum Sensor: No
Airspeed Sensor: No
NTC2 Temp Sensor: No
NTC3 Temp Sensor: No
NTC4 Temp Sensor: No
Sensor Options
Measurement Units