STULZ Ultra-Series Humidifier Controller
(August, 2013)
41
Factory Save
SENSORS
Digital In
Control Air Temp:
Enable Type: 4-20mA
Minimum X: 20.0
Maximum X: 100.0
Minimum Y: 0.0°c
Maximum Y: 100.0°c
X: 36.0 Y: 67.8°F
Control Air Humid:
Enable Type: 4-20mA
Minimum X: 20.0
Maximum X: 100.0
Minimum Y: 0.0%RH
Maximum Y: 100.0%RH
X: 36.0 Y: 67.8%RH
Conductivity
:
Enable
Scaling: Low
Internal table is
Used for scaling
Table output: 3
1024
BMS Comm
FACTORY
Sys Cfg
5.6 Factory
Configuration
The Factory menu loop may be accessed from the
Service>Factory screen. Enter the factory level password
to gain access to the loop.
Only authorized personnel who possess a thorough
understanding of the system operation should perform
modifications to the Factory menu. The menu screens
must have accurate variables entered otherwise erratic
operation may occur. These menu screens are configured
with higher password protection, thus requiring a higher
level of authority to access them. It is intended that access
to the Factory menu screens only be established while the
user is working with the guidance of STULZ Product
Support (see Section 9.0) because incorrect settings made
at that level could unintentionally damage the equipment.
The Factory Configuration menu loop contains settings for
the options that should not need to be adjusted once the
system ships from the factory. When entered using the
Service Password, all parameters are read only and
cannot be changed.
5.6.1.1 Sensor Input Setup
The Sensor inputs are analog inputs comprising of a signal
that is one of the following: 4-20 mA, 0-1 Volt, 0-5 Volt, 0-
10 Volt or an NTC sensor. The range of the input is
translated into a value for display. The Sensor Input Setup
screens define the relationship between the input (X) and
the display value (Y). The minimum value of X
corresponds to the minimum value of Y and the maximum
value of X corresponds to the maximum value of Y. The
bottom line shows the raw input (X) and the corresponding
display value (Y). Note that the minimum and maximum
values of Y for temperatures are always in Celsius. The
display value for Y is in the units selected.
The x values for 4-20 ma sensors are nominally 20.0 and
100.0. The x values for all other sensors is nominally 0.0
and 100.0
5.6.1.1.1 Control Temperature Setup
5.6.1.1.2 Control Humidity Setup
5.6.1.1.3 Conductivity
FACTORY
.
SENSOR INPUT SETUP
SENSOR INPUT SETUP
SENSOR INPUT SETUP
SERVICE MENU
software