STULZ Ultra-Series Humidifier Controller
48
(August,
2013)
Customer Alarm 3 Invert
Yes
Group Select Invert
Yes
Parameter Set
Point
Group A Limit Enable
Yes
Group B Limit Enable
Yes
Cabinet Temperature Alarm Shutdown
No
NTC2 Temperature Alarm Shutdown
No
NTC3 Temperature Alarm Shutdown
No
Custom Alarm 1 Shutdown Enable
No
Custom Alarm 2 Shutdown Enable
No
Custom Alarm 3 Shutdown Enable
No
Custom Alarm 4 Shutdown Enable
No
Cabinet Low Temperature Alarm Enable
Yes
Cabinet High Temperature Alarm Enable
Yes
NTC2 Low Temperature Alarm Enable
No
NTC2 High Temperature Alarm Enable
No
NTC3 Low Temperature Alarm Enable
No
NTC3 High Temperature Alarm Enable
No
NTC2 Low Temperature Alarm Enable
No
NTC2 High Temperature Alarm Enable
No
Humidity Limit Alarm Enable
No
Demo Case Selected
No
Control Temperature Offset
0.0°F
Control Humidity Offset
0.0%RH
Conductivity Offset
0.0 uS
Airspeed Offset
0.0 fpm
Cabinet Temperature Offset
0.0°F
NTC2 Temperature Offset
0.0°F
NTC3 Temperature Offset
0.0°F
NTC4 Temperature Offset
0.0°F
Customer Alarm 1 Shutdown Enable
No
Customer Alarm 2 Shutdown Enable
No
Customer Alarm 3 Shutdown Enable
No
Airflow Shutdown Enable
No
Control Mode
Humidity
Limit Humidity Set Point
80.0%RH
Limit Temperature Set Point
72.0°F
Startup Delay
10 Sec
Pin 4
None
Airflow Delay
5 sec
Alarm delay
10 sec
Airflow offset
0.0 fpm
dew point Cut-in
-4.0°F
dew point Cutout
0.0°F
Sensor Fail Delay
15 sec
Recovery Delay
1 sec
Limit dew point Cut-in
5.0°F
Limit dew point Cutout
0.0°F
Control Password
1
Service Password
2
Factory Password
-
System Configuration Password
-
Number of humidifiers
1
First Modbus address of Humidifiers
6
Airspeed Type
4-20mA
High Limit Humidity Alarm Set Point
95.0%RH
Low Limit Humidity Alarm Set Point
20.0%RH
Limit Humidity Alarm Offset
5.0%RH
BMS Timeout
10 sec
BMS Address
1
BMS Baud rate
19,200
BMS Protocol Select
BACnet
Control Humidity Sensor Type
4-20mA
Control Humidity Set Point
45.0%RH
Control Humidity Cut-in
-4%RH
Control Humidity Cutout
0.0%RH
Limit Humidity Sensor Type
4-20mA
Control Temperature Sensor Type
4-20mA
Parameter Set
Point
High Control Humidity Alarm
70.0%RH
Low Control Humidity Alarm
30% RH
Control Humidity Alarm Offset
5.0%RH
Drain Duration
10 mins.
Cabinet Temperature Sensor X minimum
0.0
Cabinet Temperature Sensor X minimum
100.0
Cabinet Temperature Sensor Y minimum
0.0°C
Cabinet Temperature Sensor Y minimum
100.0°C
NTC2 Temperature Sensor X minimum
0.0
NTC2 Temperature Sensor X minimum
100.0
NTC2 Temperature Sensor Y minimum
0.0°C
NTC2 Temperature Sensor Y minimum
100.0°C
NTC3 Temperature Sensor X minimum
0.0
NTC3 Temperature Sensor X minimum
100.0
NTC3 Temperature Sensor Y minimum
0.0°C
NTC3 Temperature Sensor Y minimum
100.0°C
NTC4 Temperature Sensor X minimum
0.0
NTC4 Temperature Sensor X minimum
100.0
NTC4 Temperature Sensor Y minimum
0.0°C
NTC4 Temperature Sensor Y minimum
100.0°C
Group Rotation Hours
24 hours
Humidifier Type
3
Limit Temperature Sensor Type
4-20mA
Conductivity Delay
10 sec
Group A Restrictor
100%
Group Switch Time
24 hours
Group B Restrictor
100%
Limit Humidity Cut-in
-4.0%rH
Limit Humidity Cutout
0.0%RH
Limit Temperature Cut-in
-4.0°F
Limit Temperature Cutout
0.0°F
Group B Assist
Rotate
Humidifier Modbus number of stop bits
0
Humidifier Modbus parity
None
Humidifier Modbus Baud rate
19,200
Operating Mode
2
(See Table,
Section 5.7.1)
Clock Adjust
3600
Drain hours high
0
Drain hours low part
72 hours
High Control Temperature Alarm Enable
No
Low Control Temperature Alarm Enable
No
High Control Humidity Alarm Enable
Yes
Low Control Humidity Alarm Enable
Yes
Fahrenheit is Temperature Unit of Measure
Yes
Auto Reset
Yes
Auto Reset Remote
Yes
Smoke Shutdown on Alarm
No
Drain Enable
Yes
Suppress Buzzer
Yes
High Limit Temperature Alarm Enable
No
Air Speed Units
fpm
Low Limit Temperature Alarm Enable
No
Freeze Alarm Enable
No