SYMPTOM
PROBABLE
CAUSE RECOMMENDATION
Condenser Pressure Too High
2. Valves not open or partially open.
(Cont.)
Repair/replace as needed.
3. Air in system - bleed system.
4. Check all strainers and clean if
needed.
i. Water/glycol solution not mixed prior
Remove solution and premix.
to adding to system.
Refi ll system.
Condenser Pressure
a. Loss of refrigerant (indicated by
Locate and repair leak. Recharge
too Low
bubbles in sight glass).
system.
b. Condenser fan controls not set
Adjust or repair controls.
properly.
c. Water regulating valve adjusted
Readjust to 240-250 psig.
too
low.
Noisy Compressor
a. Expansion valve stuck in open
Ensure feeder bulb is tight on suction
position (abnormally cold suction line).
line. Check operation and superheat.
b. Broken compressor valve
Replace compressor.
(compressor knocking, suction
pressure rises faster than 2lbs/min
after
shutdown).
c. Worn or scarred compressor bearings. Replace
compressor.
d. Liquid slugging.
System overcharged.
Reclaim excess refrigerant.
e. Scroll compressor not properly
Phase correctly at main power
phased.
source.
DO NOT REWIRE
COMPRESSOR.
Compressor Fails to Start
a. Thermostat set too high.
Adjust to desired temperature.
b. Compressor internal protector
Check compressor for short circuit
is open.
or ground.
c. Complete loss of refrigerant charge
Locate and repair leak. Recharge
(low pressure safety switch).
system.
d. Condenser pressure too high (high
Check condenser for obstructions.
pressure safety switch).
System Short of Capacity
a. Low refrigerant (indicated by
Check for leaks Repair and
bubbles in sight glass).
recharge system.
b. Expansion valve stuck or obstructed
Remove valve and clear obstruction
(short cycling or continuous running).
or replace valve.
c. Clogged drier/strainer (feels cold).
Replace with new drier/ strainer.
d. Reduced airfl ow. and evaporator
Check belt tension, fi lters.
coil.
4-4
Содержание CeilAiR Series
Страница 1: ... Mar 2012 CeilAiR OHS Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Страница 54: ... Mar 2012 CeilAiR OHS Series Installation Operation Maintenance Manual Air Technology Systems Inc NOTES ...
Страница 56: ... Mar 2012 CeilAiR OHS Series Installation Operation Maintenance Manual Air Technology Systems Inc ...
Страница 58: ... Mar 2012 CeilAiR OHS Series Installation Operation Maintenance Manual Air Technology Systems Inc ...