TECHNICIAN MENU
Keys
Sub-menu
Keys
Lines
Keys
Factory
settings
Field
1. ADVANCED CH
SETTINGS
C
1. CH power set
C
1. Maximum power 100%
C
100%
0 - 100%
D
B
D
2. Minimum power 0%
C
0%
0 - 100%
D
2. CH temperatures
C
1. ABS max temperature
C
80°C
20 - 85°C
D
2. CH maximum setpoint
C
75°C
20 - 85°C
D
3. CH minimum setpoint
C
40°C
20 - 70°C
D
4. CH setpoint hysteresis
C
3°C
2 - 10°C
D
3. OTC parameters
C
1. Outside temp for max CH
C
-10°C
-34 - 10°C
D
2. Outside temp for min CH
C
18°C
15 - 25°C
D
3. Outside CH temp. OFF
C
OFF
OFF /
7 - 30°C
D
4. OTC setpoint table
C
read only
D
5. OTC curve
C
read only
D
4. DHW pump settings
C
1. DHW post pump time
C
5’
1’ - 30’
D
5. CH anticycling timer
C
--->
--->
2’
0’ - 15’
D
6. DHW request type
C
Outside sensor / room
therm. / 0-10V signal [%] /
0-10V signal [SP]
C
Room
thermostat
Outside
sensor /
room therm. /
0-10V signal
[%] / 0-10V
signal [SP]
2. ADVANCED DHW
SETTINGS
C
1. DHW power
C
1. Maximum power 100%
C
100%
0-100%
D
B
D
2. Minimum power 0%
C
0%
0-100%
D
2. DHW temperature
C
1. Storage DHW setpoint
C
80°C
35-85°C
D
2. Instant DHW setpoint
C
60°C (*)
10-65°C
D
3. DHW setpoint hysteresis
C
3°C
2-10°C
D
3. DHW pump settings
C
1. DHW post pump time
C
30s
Off/1-180s
D
4. DHW priority
C
1. DHW status
C
Enabled
Enabled/
disabled
D
2. DHW priority timeout
C
Off
Off/1-60min.
D
5. DHW request type
C
--->
--->
Switch
Switch /
Sensor (*)
(*) In the event of a "sensor" type DHW request, the heating appliance heats the water to a temperature as set in point
“
2.2.2
“ of the technician menu + 20°C.
- 35
-
INST
ALLA