Grounding Considerations
C-2
Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
As shown in
, a
star ground
is often used to obtain the same earth reference
ground. Each earth reference ground, such as the system base ground, is returned
separately to a common point where a zero-volt (0V) earth ground exists. The star
ground ensures that all equipment is at the same potential and that no noise or safety
problems associated with an unpredictable or uncharacterized grounding system will
occur.
Figure C-1. Star Ground Example
1
To monitor
2
To ftServer system
3
Earth reference ground (0V)
2
1
3
Содержание ftserver 3300
Страница 1: ...Stratus Technologies R553 01 Stratus ftServer 3300 5600 and 6600 Site Planning Guide...
Страница 10: ...Tables x Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553 Table D 4 Noise Standards D 2...
Страница 14: ...Preface xiv Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 24: ...System Documentation 1 10 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 32: ...Planning for Cables 3 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 50: ...Stratus Supplied Power Cords 4 18 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 62: ...Connecting ftServer Systems Directly to a UPS 5 12 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 100: ...Rack Mountable ftServer 3300 System Specifications A 16 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 133: ...Standards Compliance Standards Compliance D 3 VCCI Note BSMI Note...
Страница 134: ...Standards Compliance D 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...
Страница 138: ...Index Index 4 Stratus ftServer 3300 5600 and 6600 Site Planning Guide R553...