17
This menu contains settings for the CutIn and CutOut,
cycles in serve mode and auger cycle times. This screen
is available to the Technician level.
Cylinder
can be changed by pressing the SEL button.
CutOut Consistency
is a number that represents how
thick or thin the product in the freezing cylinder is. Increas-
ing the setting creates a thicker product. Decreasing the
setting makes a thinner product.
CutIn Temperature
is the suction line temperature in the
cylinder when a freezing cycle will start.
Cycles Until Sleep or Cycles in Serve Mode
is the
number of freezing cycles before the freezing cylinder goes
into Sleep Mode.
Stir On
is the amount of time that the auger rotates during
the stir cycle. Stir cycles occur in Serve Mode, Standby
Mode and Sleep 2 Mode.
Stir Off
is the amount of time between stir cycles. Stir
cycles occur in Serve Mode, Standby Mode and Sleep 2
Mode.
C. Advanced Settings (1 of 2)
The Advanced Settings menu contains standby and sleep
mode adjustments and is available to the Technician level.
Press the right arrow to go to the second screen.
Cylinder
can be changed by pressing the SEL button.
The
Standby On Time
setting determines the length of the
freezing cycle in Standby Mode.
The
Standby Off Time
setting determines the length
between freezing cycles in Standby Mode.
The
Standby Time
setting determines the total amount of
time in Standby Mode.
Sleep 1 Drive On
is the amount of time that the auger
rotates during the stir cycle in Sleep 1 Mode.
Sleep 1 Drive Off
is the amount of time between stir cycles
in Sleep 1 Mode.
D. Advanced Settings (2 of 2)
The Advanced Settings menu contains standby and sleep
mode adjustments and is available to the Technician level.
Press the left arrow to go to the first screen.
Sleep 2 CutIn
is the temperature that a freezing cycle
starts in Sleep 2 Mode.
Sleep 2 CutOut
is the temperature that a freezing cycle
stops in Sleep 2 Mode.
Default Off Time
is the maximum time between freezing
cycles during Serve Mode.
E. Storage Settings (1 of 2)
This Storage Settings menu contains storage refrigeration
parameters and is available to the Technician level. Press
the right arrow to go to the second screen.
Storage CutIn
is the temperature at which the storage
refrigeration cycle starts. This is how warm it will get before
starting a storage freezing cycle.
Storage CutOut
is the temperature at which the storage
refrigeration cycle stops. This is how low the temperature
will get before ending the storage freezing cycle.
The
Storage Offset
value is added to the storage tempera-
ture reading to determine if storage refrigeration starts with
a freezing cycle. This setting helps prevent short cycling
and saves energy.
The
Storage Off
setting determines the time between
storage refrigeration cycles during a sensor failure.
The
Storage On
setting determines the length of a storage
refrigeration cycle during a sensor failure.
Содержание O231
Страница 1: ...Model O231 SERVICE MANUAL Manual No 513646 Sept 2010 ...
Страница 2: ......
Страница 10: ...4 ...
Страница 12: ...6 ...
Страница 20: ...14 ...
Страница 30: ...24 ...
Страница 58: ...52 8 7 WIRING DIAGRAMS ...
Страница 59: ...53 ...
Страница 60: ...54 ...
Страница 61: ...55 ...
Страница 62: ...56 ...