14 | Service
STOBER
186
05/2019 | ID 442790.01
14.3
Reverse documentation
If you have questions concerning commissioning and would like to contact our service department, start by first creating
reverse documentation and send this to the e-mail address of our first level support (see the chapter
14.3.1
Creating reverse documentation in a new project
ü
Your PC is connected to the drive controller.
ü
The drive controller is ready for operation.
1.
Start DriveControlSuite.
2.
Click on
Read project
.
ð
The
Adding a connection
window opens.
3.
Direct connection
tab >
IP address
column:
Activate the IP address in question or activate all listed using the context menu. Confirm your selection with
OK
.
ð
The
Assignment and live firmware update
window opens. All drive controllers connected through the previously
selected IP addresses are displayed.
4.
Online
tab:
Click on
Establish online connection
.
ð
The data connection is established and the project configuration data is transmitted from the drive controllers to
the PC.
ð
The drive controllers are created in the project tree and are active.
5.
Then in the
Assignment and live firmware update
window >
Online
tab, click on
Set all drive controllers to offline (with
reverse documentation)
.
6.
Confirm the
Reverse documentation
dialog box with
OK
.
ð
The connection is disconnected.
ð
The drive controllers are write-protected (lock status with red R).
7.
Save the project in a local directory and send the file to us.
14.3.2
Loading reverse documentation in an existing project
ü
Your PC is connected to the drive controller.
ü
The drive controller is ready for operation.
ü
A project file for your drive system already exists.
1.
Start DriveControlSuite.
2.
Click on
Open project
.
3.
Navigate to the directory and load the file.
4.
In the project menu, click
Assignment and live firmware update
.
ð
The
Adding a connection
window opens.
5.
Direct connection
tab >
IP address
column:
Activate the IP address in question or activate all listed using the context menu. Confirm your selection with
OK
.
ð
The
Assignment and live firmware update
window opens. All drive controllers connected through the previously
selected IP addresses are displayed and are ignored by default for the data synchronization.