Event 88: Control panel
The drive controller is interrupted if:
§
A29 = 0: Inactive for STOBER device controller
or
§
A540 = 0: disable drive, motor is free to rotate for CiA device controller
Response:
§
The power unit is disabled and axis movement is no longer controlled by the drive controller
§
The brakes are no longer controlled by the drive controller and engage in the event of an inactive release override
(F06)
The drive controller is interrupted with a quick stop if:
§
A29 = 1: Active for STOBER device controller
or
§
A540 = 2: slow down on quick stop ramp for CiA device controller
Response:
§
The axis is stopped by a quick stop; meanwhile, the brakes are controlled by the drive controller and remain released
§
At the end of the quick stop, the power unit is disabled and axis movement is no longer controlled by the drive
controller; the brakes are no longer controlled by the drive controller and engage in the event of an inactive release
override (F06)
Cause
Check and action
Commissioning and
parameterization computer heavily
loaded
Check the number of open windows (DS6) and the number of active programs and
reduce the number if necessary
Connection error
Check the connection and correct it if necessary
Defective network cable
Check the cable and replace it if necessary
Faulty network connection
Check the network settings and, if applicable, the switch, router or wireless
connections and correct them or contact your network service provider if necessary
Tab. 189: Event 88 – Causes and actions