12 | Diagnostics
STOBER
146
05/2019 | ID 442790.01
12.2.12
Event 41: Temp.MotorTMP
The possible effects depend on the configured level (U15):
§
2: Warning
§
3: Fault
The drive controller is interrupted if:
§
A29 = 0: Inactive for STOBER device controller
or
§
A540 = 0: disable drive, motor is free to rotate for CiA device controller
Response:
§
The power unit is disabled and axis movement is no longer controlled by the drive controller
§
The brakes are no longer controlled by the drive controller and engage in the event of an inactive release override
(F06)
The drive controller is interrupted with a quick stop if:
§
A29 = 1: Active for STOBER device controller
or
§
A540 = 2: slow down on quick stop ramp for CiA device controller
Response:
§
The axis is stopped by a quick stop; meanwhile, the brakes are controlled by the drive controller and remain released
§
At the end of the quick stop, the power unit is disabled and axis movement is no longer controlled by the drive
controller; the brakes are no longer controlled by the drive controller and engage in the event of an inactive release
override (F06)
Cause
Check and action
Motor sensor connection error
Check the connection and correct it if necessary
Wrong sensor source for X2 –
HIPERFACE DSL
Check the sensor settings and correct them if necessary (B35)
Wrong motor design
Check the design and change the motor type if necessary
Surrounding temperatures at the
motor too high
Check the surrounding temperature and adjust it if necessary
Mechanical block of the motor
Check the output and remove the block if necessary
Increased or reduced mechanical
friction
Check the service status of the mechanical system and service them if necessary
Tab. 158: Event 41 – Causes and actions