Page 8 of 41
PROGRAMMING HOT KEYS
You can program the above menu keys as follows.
●
Select the screen which you would like to assign to the key, from the group of screens
●
Press and hold the F1 key and press “Enter”. The function key has now been programmed. When you press
the relevant function key the selected screen is displayed.
You can program all the above function keys with screens from the relevant group.
Example:
In this example, we will program screen “611 Overview house
temperature” under the info function key. Go to the main menu and then
press key 6, followed by 1 and then 1 again. Press and hold F1 and press
“Enter”. The function key has now been programmed.
If you then press the
key screen 611 will be displayed.
Restoring default setting hot keys: Press and hold the F1 key and press “function key”. We can clear the
programmed
key from the example by pressing the key combination +
.
TERMINAL NUMBER IN-/OUTPUTS
The terminal number of an input/output consists of the module address, the type of input/output and a 2-digit
serial number. The module address is between 00 and 31. The type of input/output is indicated by a letter in
accordance with the table below. The serial number must be between 01 and 99 (00 means that the
input/output is not used).
Type in-/output
Letter Serial number Description
0-10V output
A
1-99
Analogue output with a range of 0-10V or 10-0V.
Relays output
B
1-99
Relay contact output (this does not include: alarm relay,
pulse outputs etc.)
Digital output
C
1-99
Opto coupler output (Max. 35Vdc 30mA).
Open-/close control
D
1-99
Open-/close control with position feedback signal.
This includes e.g. flaps with position feedback signal.
30-230Vac output
F
1-99
Analogue output with a range of 30-230Vac or 230-30Vac.
2-10V output
G
1-99
Analogue output with a range of 2-10V with position
feedback signal. Among these are modules for controlling an
EGM-100CA or EGM-250CA
Air inlet flap
H
1-99
MCA flap, a wind compensated air inlet flap
Temperature sensor
K
1-99
This includes all types of temperature sensor fitted with 10K
NTC resistor (N10B, BV10B etc.)
0-10V input
L
1-99
Analogue input with a measuring range of 0-10V. To connect
measuring sensors such as RH, CO2, pressure etc.
Digital input
M
1-99
This includes measuring fans, counter contacts etc.
Meteo station
N
1-99
Module on which a wind speed meter, wind direction and a
rain sensor can be connected to.
6
1
2
3
4
5
group number
+