1. Outside temperature is lower than the house temperature setting: The calculated alarm limit will be
increased to the maximum alarm limit
setting in keeping with the house
temperature.
2. Outside temperature is higher than the house temperature setting: The calculated alarm limit will be made
equal to the outside temperature and the
calculated alarm limit is shifted
3. Maximum alarm limit exceeds the absolute alarm limit:
The maximum alarm limit will be made
equal to the absolute alarm limit.
GROUPS TEMPERATURE
Switch the alarm on/off. The alarm limits shown are the calculated alarm limits and depend on such factors as
the preset house temperature limits and the preset temperature of the control itself.
GROUPS VENTILATION
If the measuring fan is switched off it no longer influences the control and alarm functions of the main
ventilation group. You can only switch the ventilation alarm on/off for flaps connected to a DMS or PL-9200-POT
module.
HEATING / COOLING / MISCELLANEOUS
The alarm limits can be set separately for every individual control.
THERMO-DIFFERENTIAL ALARM
(alarm temperature monitoring)
If you deactivate the temperature monitoring alarm, the current
temperature measurement result will be cleared and the alarm will be
activated again automatically. See also temperature monitoring on page
Maximum alarm limit
Minimum alarm limit
Calculated temperature
(31.0ºC)
Temperature setting
(22.0ºC)
Outside temperature compensation
(9.0ºC)
Absolute alarm limit
(35.0ºC)
(-5.0ºC)
(+5.0ºC)
(17.0ºC)
(36.0ºC)