Page 23 of 41
CO
2
In addition to the ventilation control which controls on the basis of temperature, the further functionality of the
poultry computer includes the possibility of controlling the ventilation/flap position on the basis of CO
2
. This
means that the ventilation effort will be increased if the result measured is higher than the “compensation start”
setting. 100ppm equals 1.0% increase in ventilation.
The corrected ventilation is limited
by the pre-set maximum (Max.).
Correction ventilation
Compensation = ((current CO2 – CO2 compensation start) / 100ppm ) * factor * 1%.
Factor
If 0.0 is set, this means that RH compensation does not affect the ventilation and/or the flap position. If 9.9 is
set, CO2 compensation has a maximum effect on the ventilation and/or the flap position.
If both RH compensation and CO
2
compensation are active, the highest compensation value is used for
ventilation correction.
Before cleaning the room, remove the RH-sensor and CO2 sensor and screw the
protection cap onto the extension cables.