Function
Smoke protection control unit for pressurized gas generators, for the opening
of smoke extraction covers in the case of
fi
re.
With integrated sliding switch to adjust: “active” (pressurized gas generator
switched on / active) and “secured” (pressurized gas generator switched off
and deactivated e.g. for maintenance work).
Special features
• 1 SHE group
• with integrated SHE manual call point
• 24 V power supply, emergency power batteries and charging unit, parallel
operation, 72 hours of functioning guaranteed in case of power failure
• line monitoring of alarm circuits (autom. detectors and SHE man. call points)
• line monitoring of the connected pressurized gas generator
• optical malfunction alarm
• separately fused power input 230 V AC / 50 Hz
• plastic housing for surface mounting
• dimensions 220 x 145 x 85 mm (height x width x depth)
•
fl
ush mounting option with facing frame
• hinged door, lockable (optional accessory)
• conforms to current state-of-the-arts standards
• processor controlled
• versatile connection facilities
• with integrated maintenance timer
• Service-Port-Interface included*
* The Service Port Software including the port connecting cable is required for extended con
fi
guration
possibilities, please order separately.
SHE control panel TRZ Plus DG
To connect 24 V DC pressurized gas generators
Please keep these operating instructions for future reference and maintenance. Subject to technical modi
fi
cations. Diagram is not binding.
SHE control panel TRZ Plus DG