38
04/24999499
Function of DIP-Switches
Adjustable functions for ON setting
DIP-Switch 4
: “Fire Alarm System Open” and “Reset via 1 x Fire Alarm System closer contact”
DIP-Switch 5
: Pre-alert
DIP-Switch
8
: SHE Closed (on the SHE operating station) = SHE-Reset
DIP-Switch 11
: Detector monitoring with active termination module
Attention:
Activation of the functions 1, 2, 3, 6, 7, 9 , 10 and 12 ON will cause the unit to function
incorrectly!
DIP-Switches
Attention:
All settings of the DIP-switches have to be made without current (230V AC) and without accumulator
attached.
Factory settings for the DIP-switch are position OFF. Position ON, means:
DIP-Switch 4
: “Fire alarm system Open” and “Reset via 1 x
fi
re alarm system closer contact”. Connection via the
terminals of the automatic detectors with additional UEB2 module. Fire alarm system contact closed denotes SHE
activation,
fi
re alarm system contact Open = SHE-Reset and also closure of the
fl
aps/windows. A combination with an
automatic warning device is possible, but the Reset will have to be done solely via SHE-Reset button of the TRZ Plus or
when con
fi
guration DIP-Switch 8 = ON additionally via Close-button of an SHE-manual calling point.
1 2 3 4 5 6 7 8 9
ON
10 11 12
DIP-Switch 5
: Pre-alert
A malfunction signal will take place if an automatic detector releases, if more than one automatic detector releases SHE
release will take place.
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
DIP-Switch 8
: SHE Close (on the SHE operating station) = SHE-Reset
Enables a Reset at any Type RBH/3A SHE operating station.
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
DIP-Switch 11
: Detector monitoring with active end-module
To reduce the stand-by current consumption of the detector line of the automatic detectors and for downward
compatibility for the TRZ 2A and TRZ VdS.
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12
DIP-Switches activation
When the settings of the DIP-Switches are complete the 230 V AC mains voltage is switched on or connected, as is the
emergency power battery. The new functions are transferred to the memory. For monitoring purposes a memory check is
made as soon as the control panel system is supplied with power (mains and/or battery). Provided that after approx.
3 seconds no error signal “8
fl
ashes“ (memory error) appears on the collective malfunction display, the new functions
have been successfully saved.
DIP-Switches
SHE control panel TRZ Plus DG
1 2 3 4 5 6 7 8 9
ON
10 11 12
1 2 3 4 5 6 7 8 9
ON
10 11 12