13
Flashing codes MCU
Errors recognised are emitted as a flashing sequence via the
yellow fault LED. The flashing sequences have the following
meaning:
Flash code
Error
Cause of Error
DURATION
Actuator monitoring Lines faulty
DURATION
DG switch
DG slider switch is in the
“Secured” position
Off
No error
-
Error detecting codes
LEDs permanently lit up
This fault can have two causes, either a fault in the supply in
the area of the actuator supply or the DG slider switch is in the
“secured” position.
Corrective action:
- Check whether all the cabling is OK, in particular terminals: 1, 2,
3, 10, 11.
- Check whether monitoring diodes are connected to the last MZ2
DGM (terminals: 7, 8, and 9).
- Check whether the DG slider switch is switched to “active”.
- If none of the above helps, replace the module.
Blinkcodes der DGM
Erkannte Fehler werden als Blinkfolge über die gelben Störungs
LED`s ausgegeben. Die Blinkfolgen haben folgende Bedeutung:
Blinkfolge
Fehler
Auslöser
DAUER
Aktorüberwachung Leitungen fehlerhaft
DAUER
DG Schalter
DG Schiebeschalter
steht auf Position
“gesichert”
Aus
kein Fehler
-
Fehlercodes
Dauerleuchten
Dieser Fehler kann zwei Ursachen haben, entweder die fehlerhafte
Versorgung im Bereich der Aktorversorgung oder der DG
Schiebeschalter steht in Position “gesichert”.
Abhilfe:
- Prüfen, ob die gesamte Verdrahtung in Ordnung ist,
insbesondere die Klemmen:1, 2, 3, 10, 11.
- Prüfen, ob Überwachungsdioden am letzten MZ2 DGM
angeschlossen sind (Klemme 7, 8 und 9).
- Prüfen, ob der DG Schiebeschalter auf “aktiv” geschaltet ist.
- Falls nichts hilft, Modul austauschen.