![Stephill SSD10000S Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/stephill/ssd10000s/ssd10000s_operation-manual_1372635006.webp)
SSD10000S - SSD10000S/3PH
5
Main alternator 115/230V AC outputs protected by double pole MCB.
115V - Floating Earth - Thermal reset button overload protection for each socket.
Main outputs 400V/230V protected by an RCBO.
Note
MCB = Miniature Circuit Breaker (overcurrent)
RCD = Residual Current Device
RCBO = Residual Current Device with Overcurrent Protection
All are suitably rated for the generator model type.
400V 3Ph
- Neutral (star point) bonded to earth.
230V 1Ph
- Neutral bonded to earth.
115V 1Ph
- Floating earth.
50% Load
75% Load
100% Load
10.0
10.0
AC Output & Protection - SSD10000S/3PH
(COP) Continuous Power
: Applicable for supplying power to electrical load for unlimited hours in accordance
with ISO 8528-1 under the agreed operating conditions with the maintenance intervals and procedures being
carried out as prescribed by the manufacturers.
Specification
kVA (COP)
Fuel Tank Capacity
Model Type
SSD10000S
SSD10000S/3PH
kW (COP)
Frequency
AC Output Earthing Method
Running Hours
13 hours @ 2.8 L/h
10 hours @ 3.7 L/h
25% Load
Voltage
Phase
LWA
dBA @ 7M
67
1 Ph
3 Ph
92
67
92
115 / 230V AC
400V AC
8.0
50.0 Hz
8.0
50.0 Hz
37 Litres
41 hours @ 0.9 L/h
20 hours @ 1.8 L/h
AC Output & Protection - SSD10000S
230V - Neutral bonded to Earth - RCD protection & thermal reset button overload protection for
each socket.
Содержание SSD10000S
Страница 37: ...Blank Page...