SSD10000S - SSD10000S/3PH
21
● Check the radiator fins are not obstructed/dirty.
● Check the radiator is not damaged or leaking coolant.
Coolant Level
●
Check the temperature switch operation - Ref. wiring
diagram - replace if necessary.
DO NOT USE THE
GENERATOR WITHOUT A TEMPERATURE SWITCH FITTED.
Temperature Switch
● Check associated fuel system - fuel level, fuel filters etc. -
poor engine performance can cause low oil pressure.
Low Oil Level
Fan Belt
Fault occurs after
the engine has fired
High Engine
Temperature
Canopy Obstructions
Faulty Wiring
Low Oil Pressure
● Check associated wiring from the temperature switch to
the DSE 3110 - Ref. wiring diagram.
●
Check the generator canopy has no obstructions over any
vented areas - Also see
Operating Environment
in this
handbook.
If the temperature gauge shows a high temperature (> 100
⁰C) and the generator is
shutting down with all the above checked, then the issue could be an engine
component e.g. thermostat, water pump etc. - consult an engine specialist.
Service
● Oil change and oil filter clean recommended.
When the engine is running you should expect the regulated DC voltage measured on
the battery to between 13.8 and 14.8V DC
● Check oil level and top-up to the correct level if necessary.
Fuel System
● Check wiring from the oil pressure switch to the DSE 3110 -
Ref. wiring diagram
Faulty Wiring
A
High Engine Temperature
shutdown could be for two main reasons, either the
engine has overheated or the temperature switch or wiring is faulty.
●
Check the oil pressure switch operation - Switch normally
closed when engine is at rest and open when engine running
- Remove, clean or replace if necessary.
Oil Pressure Switch
Fault Icon
Possible Cause
Check
● Check the level of the water and antifreeze level - fill with
a 50/50 mix as indicated by the sticker next to the
inspection flap.
CAUTION HOT STEAM CAN BURN!
Radiator
● Check the condition and tension of the fan belt - tighten or
replace if necessary.
Fault occurs after
the engine has fired
Battery Flat and/or
Not Charging
Charge Fail
See BATTERY CHARGE FAULT FINDING GUIDE