● Check and/or replace the main fuel filter.
● Check the connections on the capacitor.
● Test and/or replace the AC alternator capacitor.
The no-load frequency/rpm should measure approximately
52.5Hz/3150rpm.
● Check in-line fuel filter and replace if necessary.
● Check water separator filter if necessary.
● Check the condition of the air filter - Replace if necessary.
cont.
● Check the green plug with a brown & blue wire is not
loose.
● Start and run the generator and measure the AC voltage
across the brown & blue wires - this should measure
approximately
115V,
230V or 400V AC
.
DSE 3110 Control Module
Low AC Voltage
● Check the switches function and wiring on the back of the
emergency stop.
Emergency Stop
Fuel Filter(s)
Air Filter
● Check main alternator output - AC alternator tests would
be advisable.
● Check in-line fuel filter and replace if necessary.
●
Check the 40A fuse on the engine loom -
Ref. wiring
diagram
.
Fuel Filter(s)
● Check the plugs on the back of DSE 3110.
Starter Motor
Capacitor
DSE 3110 Control Module
●
Check for b output at No.4 (starter motor relay
feed) after the pre-heat time -
Ref. wiring diagram
.
●
Check the operation and wiring of the starter motor -
Replace if necessary.
Engine Not Starting/Running - Starter motor engaging but engine not starting
●
Check for continuity and wiring on the AC 2A reset button
(brown wire from DSE 3110) - Replace if necessary.
2A Reset Button
Low AC Voltage
and
Low Hz/Frequency
could indicate the engine is running too slow.
Warning
- It is not recommended to adjust the engine speed unless absolutely
necessary.
Main AC Alternator
● Check the fuel pump is receiving 12V DC and is operating -
Replace if necessary.
● Check the condition of the air filter - Replace if necessary.
● If possible run the generator from a separate fuel source
from the fuel tank.
Engine Starting/Running Then Stopping - 3 Attempts
Fuse
Fault Icon
Possible Cause
Low Hz/Frequency
Shutdown
Check
Contaminated Fuel
Fuel Lift Pump (12V DC)
Fuel Lift Pump (12V DC)
● Check that all the green plugs are fitted correctly and the
wiring.
DSE 3110 Control Module
● If possible run the generator from a separate fuel source
from the fuel tank.
● Check the fuel pump is receiving 12V DC and is operating -
Replace if necessary.
Fail to Start
Is activated after
three attempts to
start
Shutdown
Consult an engine specialist if the above fails to rectify the issue.
Consult an engine specialist if the above fails to rectify the issue.
Emergency Stop Button
Air Filter
Contaminated Fuel
DSE 3110 not showing Volts or Hz when running?
● Check if the emergency stop button has been activated.