Care, maintenance and service
The device is maintenance-free. If functional faults occur, please consult your
dealer and present the payment receipt/invoice.
X
Before cleaning, switch off all loads and switch off the master via the ro-
tary switch (setting "Off").
X
Clean casing surface periodically using a slightly moistened cloth. Do not
use solvents.
7 Technical
data
PA Link1 parallel switch box
Operating temperature
0 °C … +50 °C, under continuous load
Storage temperature
-20 °C … +70 °C
Humidity
0 % … 95 % relative humidity, non-condensing
Maximum altitude
2000 m above sea level
Degree of protection
IP 20, use in dry environment
Dimensions (W x H x D)
196 mm x 106 mm x 52 mm
Weight
0.8 kg
Connectable devices
Maximum of 4 stand-alone inverters of the same
type and variant:
• Solarix PI 500-12 (-60/-L60)
• Solarix PI 550-24 (-60/-L60)
• Solarix PI 1100-24 (-60/-L60)
• Solarix PI 1500-48 (-60/-L60)
Continuous output at AC OUT consumer output, see
table on page 17
Connections
• 4 data inputs RJ45 for Solarix PI
• 4 230 V AC or 115 V AC
1)
voltage inputs for
Solarix PI
• 230 V AC or 115 V AC
1)
consumer output
Connection data, AC OUT terminals
Conductor cross-section,
rigid/flexible
Minimum of 0.5 mm
2
to maximum of 16 mm
2
Conductor cross-section,
AWG
Minimum of AWG 20 to maximum of AWG 6
Connection data, master/slave terminals
Conductor cross-section,
solid (rigid)
Maximum of 4.0 mm
2
Conductor cross-section,
stranded (flexible)
Maximum of 2.5 mm
2
Conductor cross-section,
stranded (with ferule)
Maximum of 2.5 mm
2
1)
The voltage corresponds to the output voltage of the stand-alone inverters.
EN