5.
Check that all pins of the AC plug are free of voltage. Use a
suitable voltmeter for this (do not use a simple neon phase
checker).
NOTICE!
Risk of damage to the inverter or derating!
–
The mounting location must satisfy the fol-
lowing conditions:
–
The mounting location and immediate
environment are permanently fixed, ver-
tical, flat, non-inflammable and not
subject to constant vibration.
–
The permissible ambient conditions are
conformed to; see Technical data
Ä
Chapter 8 „Technical data“ on page 57
.
–
The following free spaces must be
present around the inverter:
Above/below: at least 200 mm
At the sides/in front: at least 60 mm
–
Do not install the inverter in areas where
animals are kept.
–
Observe the connection ratings specified on
the type plate.
–
The DC cables must not be connected to an
earth potential (DC inputs and AC output
are not galvanically isolated).
NOTICE!
When transmitting data over a public network:
–
Transmitting data over a public network may
result in additional costs.
–
Data transmitted over a public network is
not protected from unauthorised access by
third-parties.
Notice
–
Avoid exposing the inverter to direct sun-
light.
–
The display must be readable on the
installed device.
–
The inverter operates not completely noise-
lessly. Consider this when choosing an
installation location.
EN
750.661 | Z03 | 2016-09-12
31