background image

3.    Clean the filter in the control valve if necessary.

4.    Check the flue for soot and clean if necessary.  

      Check all flue joints seals and reseal if required.

5.    Check for oil leaks at all fittings.

6.    Light the stove (checking the ignition system).  

      Check that the flue stabiliser is operating cor-
      rectly and that the flame pattern is acceptable.

Blanking Nut

Fig.23

17

(c)  Check for flue or chimney blockage and clean

if required.

(d)  Do not attempt to relight the fire until the cause

of the fume emission has been identified and
corrected. If necessary seek expert advice.

The most common cause of fume emission is flueway
or chimney blockage. For your own safety
these must be kept clean at all times.

This appliance is hot while in operation and retains its
heat for a long period of time after use. Children,
aged or infirm persons should be supervised at all
times and should not be allowed to touch the hot
working surfaces while in use or until the appliance
has thoroughly cooled.

If the stove does not work properly during certain  
adverse weather conditions, switch the stove off.
Have the installation inspected by your locals service
engineer who will make recommendation on how to
rminimise the effect of adverse weather conditions on
the stove.

The flue draught stabiliser located on the back of the
stove is set by the engineer during commissioning of
the appliance. The user should not adjust the draught
stabiliser as it will effect the performance of the stove.

CO ALARM

Waterford Stanley recommend the fitting of a CO
Alarm in the same room as the appliance.
Further guidance on the installation of a carbon
monoxide alarm is available in BS EN 50292:2002
and from the alarm manufacturers instructions.
Provision of an alarm must not be considered a
substitute for either installing the appliance correctly
or ensuring regular servicing and maintenance of the
appliance and chimney system.

WARNING:-

If the CO Alarm sounds unexpectedly:-

1.

Shut off the appliance.

2.  Open Doors and windows to ventilate the room 

and then leave the premises.

FIRE SAFETY

To provide reasonable fire safety, the following
should be given serious consideration:

1.  Install a smoke detector in the room.
2.  A conveniently located class A fire extinguisher to

contend with small fires resulting from burning
embers.

3.  A practical evacuation plan.

4.  A plan to deal with a chimney fire as follows:-

(a)  Notify the fire department.

(b)  Prepare occupants for immediate 

evacuation.

(c)  Turn off the stove and the oil supply.

(d)  While awaiting the fire department watch 

for ignition to adjacent combustibles from 
overheated flue pipe or from embers or sparks
from the chimney.

WARNING:

Properly installed, operated and maintained this
stove will not emit fumes into the dwelling.

Persistent fume emission is potentially dangerous and
must not be tolerated. If fume emission does persist,
then the following immediate action should be taken:

(a) Turn off the stove
(b)  Open doors and windows to ventilate room and

then leave the premises.

Содержание Tara Mk3

Страница 1: ...nce is hot while in operation and retains its heat for a long period of time after use Children aged or infirm persons should be supervised at all times and should not be allowed to touch the hot work...

Страница 2: ...lues or Chimneys 9 16 Use of External Flues 9 17 Flue Termination Height 10 18 Flue Stabilizer 10 19 Ventilation Combustion Air Requirement 10 20 Installation Assembly 11 21 Fire Log Setup 11 22 Commi...

Страница 3: ...oat use disposable protection Installation should be carried out in a well ventilated area Any alterations to this appliance that are not approved in writing by Waterford Stanley will render the guara...

Страница 4: ...at the maximum permitted oil flow rate This appliance has been tested and approved to EN1 flued oil stoves with vaporizing burners Appliance Class 2b All technical data are taken under laboratory con...

Страница 5: ...12 inches to the front Note The hearth must be level stable and capable of supporting the stove ELECTRICAL SUPPLY All wiring external to the appliance must conform to the current B S 7671 UK B S 7462...

Страница 6: ...rewed joints must only be made with taper threads complying to B S 1740 Part 1 1971 Jointing materials must be of types intended for use with oil fuel Special petroleum resisting compounds and PTFE ta...

Страница 7: ...er and control valve A suitable shut off valve should be fitted near the stove and be accessible at all times NOTE Fuel to the appliance should be gravity fed only 7 These requirements are in accordan...

Страница 8: ...do so could result in loss in performance of the stove WARNING Only operate this appliance if connected to a properly installed flue system This stove must be connected to a 125mm 5 diam eter flue sys...

Страница 9: ...RNAL FLUES OR CHIMNEYS When connecting the stove to an existing chimney or internal flue the flue system must adhere to all the fol lowing requirements See Fig 11 1 The horizontal flue section exiting...

Страница 10: ...upply to the flue whenever the flue s negative pressure reaches its upper limit and so pre vents the negative pressure in the stove rising above its optimum level The flue stabiliser should be ad just...

Страница 11: ...Level the stove in all directions using the level ling screws on the stove legs 5 Connect the fuel line to the oil control valve and reset the control valve trigger as shown in Fig 17 6 Check all joi...

Страница 12: ...perature i e at maximum setting adjust the draught regulator until the desired flame pattern is achieved 5 Using the flue sampling point See Fig 19 check that the Bacharach smoke number is not greater...

Страница 13: ...op of oil falls into the vessel 3 Measure the oil flow for 5 minutes Consult the Technical Data section for the correct rate 4 Turn the control valve to 1 and repeat the above procedure 5 If either of...

Страница 14: ...X 26 HOLD BRACKET F01142AXX 27 BOTTOM SHIELD SUPPORT BKT F01095AXX 28 SPACER V00033AXX 29 AIR WASH KNOB U00077AXX 30 TERRY CLIP W00921AXX 31 ISOLATING TRANSFORMER G00506AXX 32 STRAIN RELIEF CABLE GLAN...

Страница 15: ...ustible materials and soft furnishings well away from the stove See Clearance to Combustibles section WARNING Unauthorised modification of the stove will void the product warranty Do not tamper with t...

Страница 16: ...es on setting no 2 the control lever can be adjusted to setting no 4 The flame should be allowed to sta bilise at setting no 4 for another 10 minutes prior to adjusting the control to setting No 6 Max...

Страница 17: ...t the draught stabiliser as it will effect the performance of the stove CO ALARM Waterford Stanley recommend the fitting of a CO Alarm in the same room as the appliance Further guidance on the install...

Страница 18: ...ly with a soapy damp cloth followed by a polish with a clean dry duster 2 For stubborn deposits a soap impregnated pad can be carefully used on the vitreous enamel 3 Use only products recommended by t...

Страница 19: ...locked Bleed fuel line Excessive flame noise Incorrect chimney draught Check joint seals increase height of chimney adjust draught regulator Incorrect fuel input rate Check fuel input rates adjust if...

Страница 20: ...DP 160104 Rev 002 N00557AXX Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 www waterfordstanley com 20...

Отзывы: