NOTE:   It is imperative that the stove is not rated
above the maximum flow rate as to do so will
raise the operating temperature of the stove
which could damage the control equipment or
the stove itself.

Low Rate Adjustment

High Rate 
Adjustment

Fig.21

2.    Place the collection vessel beneath the inlet pipe

      to catch the oil.  Turn the control valve to 6 
      and start the stopwatch when the first drop of oil
      falls into the vessel.

3.    Measure the oil flow for 5 minutes (Consult the 

      Technical Data section for the correct rate).

4.    Turn the control valve to 1 and repeat the above

      procedure.

5.    If either of the above input rates are not correct, 

      the control valve can be adjusted to give the 
      required rate (see Fig.21).  They should only 
      require slight adjustment and the measurement 
      procedure described in 2, 3 & 4 above should be
      followed to check each adjustment.

6.    When the required input rate is achieved, 

      reassemble the compression fitting ensuring 
      that there are no leaks and that the burner is 
      level.

Содержание Tara Mk3

Страница 1: ...nce is hot while in operation and retains its heat for a long period of time after use Children aged or infirm persons should be supervised at all times and should not be allowed to touch the hot work...

Страница 2: ...lues or Chimneys 9 16 Use of External Flues 9 17 Flue Termination Height 10 18 Flue Stabilizer 10 19 Ventilation Combustion Air Requirement 10 20 Installation Assembly 11 21 Fire Log Setup 11 22 Commi...

Страница 3: ...oat use disposable protection Installation should be carried out in a well ventilated area Any alterations to this appliance that are not approved in writing by Waterford Stanley will render the guara...

Страница 4: ...at the maximum permitted oil flow rate This appliance has been tested and approved to EN1 flued oil stoves with vaporizing burners Appliance Class 2b All technical data are taken under laboratory con...

Страница 5: ...12 inches to the front Note The hearth must be level stable and capable of supporting the stove ELECTRICAL SUPPLY All wiring external to the appliance must conform to the current B S 7671 UK B S 7462...

Страница 6: ...rewed joints must only be made with taper threads complying to B S 1740 Part 1 1971 Jointing materials must be of types intended for use with oil fuel Special petroleum resisting compounds and PTFE ta...

Страница 7: ...er and control valve A suitable shut off valve should be fitted near the stove and be accessible at all times NOTE Fuel to the appliance should be gravity fed only 7 These requirements are in accordan...

Страница 8: ...do so could result in loss in performance of the stove WARNING Only operate this appliance if connected to a properly installed flue system This stove must be connected to a 125mm 5 diam eter flue sys...

Страница 9: ...RNAL FLUES OR CHIMNEYS When connecting the stove to an existing chimney or internal flue the flue system must adhere to all the fol lowing requirements See Fig 11 1 The horizontal flue section exiting...

Страница 10: ...upply to the flue whenever the flue s negative pressure reaches its upper limit and so pre vents the negative pressure in the stove rising above its optimum level The flue stabiliser should be ad just...

Страница 11: ...Level the stove in all directions using the level ling screws on the stove legs 5 Connect the fuel line to the oil control valve and reset the control valve trigger as shown in Fig 17 6 Check all joi...

Страница 12: ...perature i e at maximum setting adjust the draught regulator until the desired flame pattern is achieved 5 Using the flue sampling point See Fig 19 check that the Bacharach smoke number is not greater...

Страница 13: ...op of oil falls into the vessel 3 Measure the oil flow for 5 minutes Consult the Technical Data section for the correct rate 4 Turn the control valve to 1 and repeat the above procedure 5 If either of...

Страница 14: ...X 26 HOLD BRACKET F01142AXX 27 BOTTOM SHIELD SUPPORT BKT F01095AXX 28 SPACER V00033AXX 29 AIR WASH KNOB U00077AXX 30 TERRY CLIP W00921AXX 31 ISOLATING TRANSFORMER G00506AXX 32 STRAIN RELIEF CABLE GLAN...

Страница 15: ...ustible materials and soft furnishings well away from the stove See Clearance to Combustibles section WARNING Unauthorised modification of the stove will void the product warranty Do not tamper with t...

Страница 16: ...es on setting no 2 the control lever can be adjusted to setting no 4 The flame should be allowed to sta bilise at setting no 4 for another 10 minutes prior to adjusting the control to setting No 6 Max...

Страница 17: ...t the draught stabiliser as it will effect the performance of the stove CO ALARM Waterford Stanley recommend the fitting of a CO Alarm in the same room as the appliance Further guidance on the install...

Страница 18: ...ly with a soapy damp cloth followed by a polish with a clean dry duster 2 For stubborn deposits a soap impregnated pad can be carefully used on the vitreous enamel 3 Use only products recommended by t...

Страница 19: ...locked Bleed fuel line Excessive flame noise Incorrect chimney draught Check joint seals increase height of chimney adjust draught regulator Incorrect fuel input rate Check fuel input rates adjust if...

Страница 20: ...DP 160104 Rev 002 N00557AXX Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 www waterfordstanley com 20...

Отзывы: