NEC Power-Limited Wiring Requirements:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least
0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter
and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power- limited applications, use of conduit is optional. All field wiring connections
must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted
adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections.
Note
Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Figure 5).
Figure 5
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Figure 6