background image

       

02140-11-E

 

Copyright

©

 Stanley Security, Inc. 2014

 9/9

Appendix A - UL Listed Compatible Devices

A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with PS161-6 output.

System Sensor
Smoke Detector/Base 

Detector Type

Max Stand-by 
Current (mA)

Alarm Current 
(mA)

B112LP

Base

0.12

36

DH100ACDC

Photoelectric

0.15

0.70

DH100ACDCLP

Photoelectric

0.15

0.70

DH100ACDCLPW

Photoelectric

0.15

0.70

DH400ACDCI

Ionization Duct

25

95

DH400ACDCP

Photoelectric Duct

25

95

1112/24/D

Ionization

0.05

50

1424

Ionization

0.10

41

1451 (w/B402B Base)

Ionization

0.10

39

2112/24ATR

Photoelectric

0.50

60/70

2112/24AITR

Photoelectric

0.50

60/70

2112/24/D

Photoelectric

0.05

50

2112/24T/D

Photoelectric w/135o Thermal

0.05

50

2112/24TSRB

Photoelectric w/135o Thermal Supervisory Relay

15

45

2312/24TB

Photoelectric

0.12

50

2412 (12 volt)

Photoelectric

0.12

77

2424

Photoelectric

0.10

41

2451

Photoelectric

0.10

39

2451TH (with/B402B Base)

Photoelectric

0.10

39

2W-MOD

Loop Test/Maintenance Mod.

30

50

4W-B (12/24 volt)

Photoelectric I3

.05

23

4WT-B (12/24 volt)

Photoelectric I3 w/Therm

.05

23

4WTA-B (12/24 volt)

I3 Photo w/Therm/Sounder

.05

35

4WTR-B (12/24 volt)

I3 Photo w/Therm/Relay

.05

35

4WITAR-B (12/24 volt)

I3 Photo w/Isolated Therm/Sounder/Relay

.05

50

6424

Projected Beam

10

28.4

Beam 1224(S)

Projected Beam

17

38.5

A.2  Relays

Table A-2 below lists relays compatible with PS161-6 output.

Manufacturer

Model

Current (mA)

Manufacturer

System Sensor

EOLR-1

30

System Sensor

For assistance or warranty information:

Call 1-855-365-2407 or visit

www.stanleysecurity.com/precision

Warning: This Manufacturer advises that no lock can provide complete security by itself. This lock may be defeated by forcible or technical means, 
or evaded by entry elsewhere on the property. No lock can substitute for caution, awareness of your environment, and common sense. Builder’s 
hardware is available in multiple performance grades to suit the application. In order to enhance security and reduce risk, you should consult a 
qualified locksmith or other security professional.

Содержание PS161-6

Страница 1: ...V AC 60HZ Current 3 5A AC Input fuse ratings 5A 250V Battery fuse ratings 7 5A 32V Output Voltage 20 0 26 4V Total output 6 amps Power limit output 2 amps per channel Outputs 8 For Delayed Egress appl...

Страница 2: ...vised on the PS161 6 board or the unit will remain in fire alarm condition 7 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Страница 3: ...is fully charged check specified voltage 24VDC 26 4 both at the battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum ch...

Страница 4: ...gative DC power outputs Figure 2 PS161 6 Board configuration Trouble Time Limited Warning of Stand by Batteries For compliance with ULC S318 96 the Time Limited Warning circuit must be connected for l...

Страница 5: ...econd leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked BAT FAIL C NO Power Distribution Module Figure 4 PD8ULCB Power Distribution Board Po...

Страница 6: ...enclosure Green Lead ground Power limited 120VAC power mains Non Power limited Battery AC Supervision Circuit Power limited Battery Connections Non Power limited Optional Rechargeable Stand by Batter...

Страница 7: ...fferent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM o...

Страница 8: ...0 279mm 12 5 318mm 4 85 123mm 1 20 31mm 1 40 36mm 5 10 130mm 6 57 167mm 1 40 36mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 13 0 330mm 1 0 25mm 3 25 83mm Edge of Enclosure Enclosure Sentrol Model 3012 Ta...

Страница 9: ...1TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 05 23 4WTA B 12 24 volt I3 Photo w The...

Отзывы: