Figure 3 - Battery trouble indication

For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a UL Listed, power-limited power source to the 
indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, 
NO].

Power Distribution Module:

Figure 4 - PD8ULCB - Power Distribution Board 
Power-Limited Outputs

NC  C  NO 

NC  C  NO

BAT FAIL

AC FAIL

POWER

SOURCE

RED INDICATING

LAMP

N

C O M M O N       P O W E R       O U T P U T S

P

F U S E D         P O W E R         O U T P U T S

1  

2  

3  

4  

5  

6  

7  

8

D1

INPUT

R1

LED

From Power Supply

Board

(Factory Installed)

DC Output to devices

1P-8P Power Outputs,

1N-8N Common Outputs

(

)

Содержание PS161-6

Страница 1: ...V AC 60HZ Current 3 5A AC Input fuse ratings 5A 250V Battery fuse ratings 7 5A 32V Output Voltage 20 0 26 4V Total output 6 amps Power limit output 2 amps per channel Outputs 8 For Delayed Egress appl...

Страница 2: ...vised on the PS161 6 board or the unit will remain in fire alarm condition 7 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Страница 3: ...is fully charged check specified voltage 24VDC 26 4 both at the battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum ch...

Страница 4: ...gative DC power outputs Figure 2 PS161 6 Board configuration Trouble Time Limited Warning of Stand by Batteries For compliance with ULC S318 96 the Time Limited Warning circuit must be connected for l...

Страница 5: ...econd leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked BAT FAIL C NO Power Distribution Module Figure 4 PD8ULCB Power Distribution Board Po...

Страница 6: ...enclosure Green Lead ground Power limited 120VAC power mains Non Power limited Battery AC Supervision Circuit Power limited Battery Connections Non Power limited Optional Rechargeable Stand by Batter...

Страница 7: ...fferent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM o...

Страница 8: ...0 279mm 12 5 318mm 4 85 123mm 1 20 31mm 1 40 36mm 5 10 130mm 6 57 167mm 1 40 36mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 13 0 330mm 1 0 25mm 3 25 83mm Edge of Enclosure Enclosure Sentrol Model 3012 Ta...

Страница 9: ...1TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 05 23 4WTA B 12 24 volt I3 Photo w The...