Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1 and with all 
local codes and authorities having jurisdiction.  The product must be located indoors within the protected premises. 

1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two 

upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, 
level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place 
the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure 
Dimensions, pg. 8).

2.  Secure enclosure to earth ground. 
3.  Set the DC output voltage to 24DC by setting SW1 to the open position on the power supply board (Figure 2-1a).
4.  Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Figure 1). Use 18 AWG for all power connections and 18 AWG 

to 22 AWG for power limited circuits (AC Fail/Low Battery reporting). Secure green wire lead to earth ground. Keep power-limited wiring 
separate from non power-limited wiring  (120VAC 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. 

5.  Measure output voltage before connecting devices. This helps avoid potential damage.
6.  Connect the delayed egress exit device locking hardware positive leads to terminals marked 1 through 4 POS (+) on the PD8ULCB board 

and negative leads to the NEG 1 terminals through 4 terminals.

Figure 1 - Wiring Diagram for Connecting DE Exit Devices to a PS161-6 Power Supply

Note 

A 10k EOL (End of Line) Resistor must be installed across terminals marked (Trigger EOL Supervised) on the PS161-6 board or the 
unit will remain in fire alarm condition.

7.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. 

Batteries must be lead acid or gel type if used. Use two 12VDC batteries connected in series for 24VDC operation (Battery leads included).

8.  Connect battery to terminals marked [--  BAT + ] (Figure 2 - 1g). Use two (2) 12VDC batteries connected in series for 24VDC operation 

(battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) 
batteries or UL recognized BAZR2 batteries of an appropriate rating.

9.  To trigger the power supply from a fire alarm control panel (FACP), connect signaling circuit of FACP to terminals marked Trigger End of 

Line Supervised.

10. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Figure 2 - 1c).
11. To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Figure 2 - 1c).

Note 

Must be set to ON position for Burglar Alarm Applications.

Delayed Egress 
Exit Device #1

Delayed Egress 
Exit Device #2

Delayed Egress 
Exit Device #3

Delayed Egress 
Exit Device #4

L

G

N

NC

C

NO

NC

C

NO

BAT

 

FAIL

AC 

FAIL

---   DC   +

AC

DC

---  BAT +

–  AUX  

TRI

GGE

R   

 EOL

SUPE

RVISED

5A 250V

RES

ET

GND

    

   N

O

Disable

Enable

2 hr.

1 min.

AC DELAY

SHUTDOWN

O N

N

C

O

M

M

ON  

 POWER

   

O

U

T

PU

TS

P

FUSED

   

 POWER   

 OUTPU

TS

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

D1

INPUT

R1

LED

Divider

DC Output to Devices
(1P-8P Power Outputs)
(1N-8N Common Outputs)

AC1

Battery & AC 
Supervision Circuit 
(Power-limited)

Potentiometer

Power-limited

Green Lead 
(Ground)

120VAC Power Mains 
(Non Power-limited)

From Power Supply Board 
(Factory Installed)

Open - 24V
Closed - 12V

Switch Detail

Closed - 12V

Open - 24V

Battery 

Connections 

(Non 

Power-limited)

12VDC Rechargeable 
Battery

+

12VDC Rechargeable 
Battery

+

No Fire 

Connections

N.O.  Input 

from

Fire Panel

N.C.  Input 

from 

Fire Panel

OR

OR

10K EOL

10K EOL

10K EOL

Separation of power- 
limited wiring from 
non power-limited 
wiring must be at 
least 1/4 inch.

Power must be 
turned off 
before changing 
the voltage 
select switch.

Содержание PS161-6

Страница 1: ...V AC 60HZ Current 3 5A AC Input fuse ratings 5A 250V Battery fuse ratings 7 5A 32V Output Voltage 20 0 26 4V Total output 6 amps Power limit output 2 amps per channel Outputs 8 For Delayed Egress appl...

Страница 2: ...vised on the PS161 6 board or the unit will remain in fire alarm condition 7 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Страница 3: ...is fully charged check specified voltage 24VDC 26 4 both at the battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum ch...

Страница 4: ...gative DC power outputs Figure 2 PS161 6 Board configuration Trouble Time Limited Warning of Stand by Batteries For compliance with ULC S318 96 the Time Limited Warning circuit must be connected for l...

Страница 5: ...econd leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked BAT FAIL C NO Power Distribution Module Figure 4 PD8ULCB Power Distribution Board Po...

Страница 6: ...enclosure Green Lead ground Power limited 120VAC power mains Non Power limited Battery AC Supervision Circuit Power limited Battery Connections Non Power limited Optional Rechargeable Stand by Batter...

Страница 7: ...fferent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM o...

Страница 8: ...0 279mm 12 5 318mm 4 85 123mm 1 20 31mm 1 40 36mm 5 10 130mm 6 57 167mm 1 40 36mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 13 0 330mm 1 0 25mm 3 25 83mm Edge of Enclosure Enclosure Sentrol Model 3012 Ta...

Страница 9: ...1TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 05 23 4WTA B 12 24 volt I3 Photo w The...

Отзывы: