 Stanley Security, Inc. 2014

 4/9

Bat Fail
NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Figure 2 - 1b).

– BAT +

Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Figure 2 - 1g).

Terminal Identification:

Power Distribution Module

Terminal Legend

Function/Description

1P to 8P

Positive DC power outputs

1N to 8N

Negative DC power outputs

Figure 2 - PS161-6 Board configuration

Trouble/Time Limited Warning of Stand-by Batteries:

For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED 
to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail 
relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel.  The following figure shows the circuitry needed for local 
annunciation.

L

G

N

NC  C  NO 

NC  C  NO

BAT FAIL

AC FAIL

---  DC  +

AC

AC1

DC

--- 

BA

T +

+ AUX –

enable
disable

1 min.
2 hr.

AC DELAY   SHUTDOWN

TRIGGER EOL

SUPERVISED

NO          GND

RESET

OPEN   

--- 

  24V

CLOSED   

---   12V

O

N

5A 250V

1a

1b

1g

1h

1e

1f

1d

1c

1i

Содержание PS161-6

Страница 1: ...V AC 60HZ Current 3 5A AC Input fuse ratings 5A 250V Battery fuse ratings 7 5A 32V Output Voltage 20 0 26 4V Total output 6 amps Power limit output 2 amps per channel Outputs 8 For Delayed Egress appl...

Страница 2: ...vised on the PS161 6 board or the unit will remain in fire alarm condition 7 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Страница 3: ...is fully charged check specified voltage 24VDC 26 4 both at the battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum ch...

Страница 4: ...gative DC power outputs Figure 2 PS161 6 Board configuration Trouble Time Limited Warning of Stand by Batteries For compliance with ULC S318 96 the Time Limited Warning circuit must be connected for l...

Страница 5: ...econd leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked BAT FAIL C NO Power Distribution Module Figure 4 PD8ULCB Power Distribution Board Po...

Страница 6: ...enclosure Green Lead ground Power limited 120VAC power mains Non Power limited Battery AC Supervision Circuit Power limited Battery Connections Non Power limited Optional Rechargeable Stand by Batter...

Страница 7: ...fferent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM o...

Страница 8: ...0 279mm 12 5 318mm 4 85 123mm 1 20 31mm 1 40 36mm 5 10 130mm 6 57 167mm 1 40 36mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 13 0 330mm 1 0 25mm 3 25 83mm Edge of Enclosure Enclosure Sentrol Model 3012 Ta...

Страница 9: ...1TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 05 23 4WTA B 12 24 volt I3 Photo w The...

Отзывы: