12. To enable Low Output Power Shutdown set dip switch [Shutdown] to ON position (Figure 2 - 1c).
13. To disable Low Output Power Shutdown set dip switch Shutdown] to OFF position (Figure 2 - 1c).
14. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to 

shutdown (Figure 2 - 1d).

15. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Figure 2 - 1e).
16. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide 

tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Figure 4 or Figure 5). Connect tamper switch wiring 
to the Access Control Panel input or the appropriate UL Listed reporting device.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note 

Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions, the DC output voltage should be checked for proper voltage level PS161-6: 24VDC nominal 

rated @ 6 amp max.

Battery Test:

 Under normal load conditions check that the battery is fully charged, check specified voltage (24VDC @ 26.4) both at the battery 

terminal and at the board terminals marked [--  BAT + ] to ensure that there is no break in the battery connection wires.

Note 

Maximum charging current under discharges is 1.54 amp.

Note 

Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Terminal Identification:

Power Supply/Charger

Terminal Legend

Function/Description

L, N

Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) (Figure 2 - 1a).

– DC +

12VDC or 24VDC nominal @ 6 amp continuous output (non power-limited output) (Figure 2 - 1h).

Trigger EOL
Supervised

Fire Alarm Interface trigger input from a short or FACP.  Trigger inputs can be normally open, normally closed from an FACP 
output circuit (power-limited input) (Figure 2 - 1d).

NO, GND
RESET

FACP interface latching or non-latching (power-limited) (Figure 2 - 1e).

+ AUX – 

Auxiliary Power-Limited output rated @ 1 amp (unswitched) (power-limited output) (Figure 2 - 1f).

AC Fail 
NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is 
present. Contact rating 1 amp @ 30VDC (power-limited) (Fig. 1b).

Содержание PS161-6

Страница 1: ...V AC 60HZ Current 3 5A AC Input fuse ratings 5A 250V Battery fuse ratings 7 5A 32V Output Voltage 20 0 26 4V Total output 6 amps Power limit output 2 amps per channel Outputs 8 For Delayed Egress appl...

Страница 2: ...vised on the PS161 6 board or the unit will remain in fire alarm condition 7 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Страница 3: ...is fully charged check specified voltage 24VDC 26 4 both at the battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum ch...

Страница 4: ...gative DC power outputs Figure 2 PS161 6 Board configuration Trouble Time Limited Warning of Stand by Batteries For compliance with ULC S318 96 the Time Limited Warning circuit must be connected for l...

Страница 5: ...econd leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked BAT FAIL C NO Power Distribution Module Figure 4 PD8ULCB Power Distribution Board Po...

Страница 6: ...enclosure Green Lead ground Power limited 120VAC power mains Non Power limited Battery AC Supervision Circuit Power limited Battery Connections Non Power limited Optional Rechargeable Stand by Batter...

Страница 7: ...fferent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM o...

Страница 8: ...0 279mm 12 5 318mm 4 85 123mm 1 20 31mm 1 40 36mm 5 10 130mm 6 57 167mm 1 40 36mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 13 0 330mm 1 0 25mm 3 25 83mm Edge of Enclosure Enclosure Sentrol Model 3012 Ta...

Страница 9: ...1TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 05 23 4WTA B 12 24 volt I3 Photo w The...

Отзывы: