GB & IE version
33
All Diagrams for illustration purposes only - Not to Scale
Minimum Vertical Flue Height: 0.5m
Maximum Vertical Flue Height: 15m
Flue calculations when using elbows
(0-90° permissible), total flue length maximum = 15m and each
bend will equate to ½m, Vertical rise (V) must be at least twice the Horizontal run (R), i.e. V=2H (or
H/V
≤½).
Waterford Stanley Flue OPTION 3 Rear Exit Snorkel
Please Note – The Maximum
length of the Horizontal flue is
550mm as per the drawing
across
Diagram for illustration purposes only -
Not to Scale
This rear kit is called a Snorkel, this can only be used when the stove is being fitted to an outside wall,
the horizontal pipe can be no longer than 550mm long (this pipe is telescopically adjustable)
For this you need to move the 2 x flue collars onto the rear of the stove and move the 2 x blanking plates
to the top of the stove, you will also need to order from a blanking plate for the top plate lid of the stove.
Flue Option 3 – Rear Exit Snorkel
Description Part No
BALANCED FLUE SNORKEL Stainless Steel
34100499
Adjustable
350-550
Содержание ARGON F650
Страница 13: ...GB IE version 13...
Страница 15: ...GB IE version 15 Remote Control Operating Instructions continued...
Страница 17: ...GB IE version 17 Remote Control Operating Instructions continued...
Страница 55: ...GB IE version 55 Appendix 1 Fault Finding Chart...
Страница 56: ...Installation Operating Manual for Argon F650 F900 Balanced Flue Gas Stoves 56 Natural Gas LPG Models...
Страница 57: ...GB IE version 57...
Страница 61: ...GB IE version 61 ARGON F650 Balanced Flue Gas LPG Waterford Stanley ARGON F650 Balanced Fuel Gas LPG 4 4...
Страница 63: ...GB IE version 63 ARGON F900 Balanced Flue Gas LPG Waterford Stanley ARGON F900 Balanced Fuel Gas LPG 6 3...